4-14 Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network

Chapter Summary

In this chapter you learned about input, output and configuration files
for the analog I/O modules on ControlNet. Move to Chapter 5 to learn
how to calibrate your module

Configuration

Word 1 cont.

Bits 14-15

(16-17)

Input Type Select

Bit

15

14

Input type selection for channels 4-7

0

0

Thermocouple

0

1

RTD

1

0

Not used

1

1

Configuration

Word 2

00-15 (00-17)

RTD loop resistance offset select bits – used input type is set to RTD and sensor mode select is set to
2-wire with loop resistance compensation. Allows you to set the type of RTD loop resistance compensation
used for all RTDs or one of three fixed values for all channels. NOTE: Not applicable to 10

copper RTD,

which defaults to 0

.

Bit

01

00

RTD channel 0

Bit

03

02

RTD channel 1

Bit

05

04

RTD channel 2

Bit

07

06

RTD channel 3

Bit

09

08

RTD channel 4

Bit

11

10

RTD channel 5

Bit

13

12

RTD channel 6

Bit

15

14

RTD channel 7

0

0

Use channel loop compensation value stored during calibration procedure for
2-wire RTD (default = 0

)

0

1

5

1

0

10

1

1

15

Configuration

Word 3

00-07

Module command data bits – These bits are written to the module during calibration. They are used to
define offset, gain and general channel calibration.

08-14 (10-16)

Module command bits – These bits are written to the module during calibration. They are used to select
channel calibration action.

15 (17)

Reserved for factory use only.

Configuration

Word

Dec. Bits

(Octal Bits)

Description