Programming the flex ex i/o modules using rio, What this chapter contains, Enter block transfer instructions – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual
Page 75: Appendix b
 
1
Publication 1797-6.5.2 - February 2001
Appendix
B
Programming the FLEX Ex I/O Modules
Using RIO
What this Chapter Contains
Read this appendix to program the 1797-IRT8 thermocouple/RTD/mV 
input module.
Enter Block Transfer
Instructions
The FLEX Ex thermocouple/RTD/mV modules communicate with the 
PLC processor through bidirectional block transfers. This is the 
sequential operation of both read and write block transfer instructions.
Before you configure the module, you need to enter block transfer 
instructions into your ladder logic. The following example programs 
illustrate the minimum programming required for communication to 
take place between the module and a PLC processor. These programs 
can be modified to suit your application requirements.
A configuration block transfer write (BTW) is initiated when the 
module is first powered up, and subsequently only when the 
programmer wants to enable or disable features of the module. The 
configuration BTW sets the bits which enable the programmable 
features of the module, such as filters and signal ranges, etc. Block 
transfer reads are performed to retrieve information from the module.
Block transfer read (BTR) programming moves status and data from 
the module to the processor’s data table. The processor user program 
initiates the request to transfer data from the module to the processor. 
The transferred words contain module status, channel status and input 
data from the module.
Your program should monitor status bits, block transfer read and 
block transfer write activity.