Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network 4-3

Scheduled Data-Transfer

Scheduled data transfer:

is continuous.

is asynchronous to the controller program scan.

occurs at the actual rate displayed in the Actual Packet Interval
field on the programming software ControlNet I/O mapping
(monitor) screen

Unscheduled Data-Transfer

Unscheduled operations include:

unscheduled non-discrete I/O data transfers–through ControlNet
I/O Transfer (CIO) instructions

peer-to-peer messaging–through message (MSG) instructions

messaging from programming devices

Unscheduled messaging on a ControlNet network is
non-deterministic. Your application and your configuration–number of
nodes, application program, NUT, amount of scheduled bandwidth
used, etc.–determine how much time there is for unscheduled
messaging.

Module I/O Mapping

The I/O map for a module is divided into read words and write
words. Read words consist of input and status words, and write
words consist of output and configuration words. The number of
read words or write words can be 0 or more. The length of each I/O
module’s read words and write words vary in size depending on
module complexity. Each I/O module will support at least 1 input
word or 1 output word. Status and configuration are optional,
depending on the module.