Publication 1797-6.5.2 - February 2001

A-4 Specifications

€

The entity concept allows interconnection of intrinsically safe

apparatus with associated apparatus not specifically examined in
combination as a system when the approved values of V

t

and I

t

of the

associated apparatus are less than or equal to V

oc

and I

sc

or V

max

and I

max

of the intrinsically safe apparatus and the approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+ C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

ó

Simple apparatus is defined as a device which neither generates

nor stores more than 1.2V, 0.1A, 20

µ

J, or 25mW.

ì

Wiring methods must be in accordance with the National Electric

Code, ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric
Code CSA C22.1, Part 1, Appendix F. For additional information refer
to ANSI/ISA RP12.6.

ö

This module, 1797-IRT8, must be used with terminal base

1797-TB3 or 1797-TB3S.

ú

Terminals 36 and 49 shall not be connected.

÷

WARNING: Substitution of components may impair intrinsic

safety.
AVERTISSEMENT: La substitution de composant peut compromettre
la securite intrinseque.

1797- IRT8

Allen-Bradley

B

-

A

7

PWR

6

5

4

3

2

1

0

2

8 Point RTD/Thermocouple mV Input Module

FLEX Ex Temperature
Input I/O Module

LEDs

Female Bus
Connection

Field Wiring
Terminals

Terminal Base

Terminal Base
Key

Male Bus
Connection

Key Position for
Terminal Base
Insertion

Note: A terminal base may not have an I/O module installed

.