Underrange alarm -8, Underrange alarm, Irt8 specific alarming performance – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual

Page 22: Sensor type

Advertising
background image

Publication 1797-6.5.2 - February 2001

2-8 Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features

Underrange Alarm

The channel underrange alarm is set if the input is less than the
minimum temperature (thermocouple or RTD range dependent),
millivolt (-40mV) or resistance (0

) range value.

Range: 0 = normal, 1 = input overrange. Default = 0.

This alarm stays active at any value below 0% of range and is always
enabled by the module.

Range: 0 = normal, 1 = input overrange. Default = 0.

normal signal range

overrange

CJC fault

underrange

-200C

+870C

IEC PT100

~ 520ohm equivalent

PHYSICAL INPUT SIGNAL RANGE

Sensor Type

-200C

+400C

IEC PT200

-200C

+630C

JIS PT100

-200C

+400C

JIS PT200

-60C

+250C

DIN Ni100

-60C

+200C

DIN Ni200

-80C

+320C

Minco Ni120

-200C

+260C

Minco Cu10

0ohm

500ohm

0-500 Resistance

-40mV

+100mV

millivolt

~ 210mV

300C

+1800C

B

-250C

+1000C

E

-210C

+1200C

J

-250C

+1372C

K

-200C

+800C

TXK/XK(L)

-250C

+1300C

N

0C

+1768C

R

0C

+1768C

S

-250C

+400C

T

Channel

Data

Forced

to

Maximum

for Type

-20C

100C

Cold Junction Compensation

CJC fault

open wire fault

~ 520ohm equivalent
~ 520ohm equivalent

~ 520ohm equivalent

~ 520ohm equivalent

~ 520ohm equivalent

~ 520ohm equivalent

~ 520ohm equivalent

~ 520ohm

~ 210mV equivalent

~ 210mV equivalent

~ 210mV equivalent

~ 210mV equivalent

~ 210mV equivalent

~ 210mV equivalent

~ 210mV equivalent
~ 210mV equivalent
~ 210mV equivalent

IRT8 Specific alarming performance