Power supply considerations -9, Safe area hazardous area, Power supply considerations – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual

Page 63

Advertising
background image

Publication 1797-6.5.2 - February 2001

Applying FLEX Ex Thermocouple/RTD/mV Input Modules 6-9

Each power supply output in the FLEX Ex system is rated for 8.5W.
Modules can be attached to the output until their combined power
equals that number. Do not exceed the power supply maximum of
8.5W.

Assign the next module to another output as before. When all four
power supply outputs are utilized, add another power supply to the
system, see the figure below.

Power Supply Considerations

When applying power, consider the certain characteristics of the wire
connecting the power supply output to a module’s power input. The
wire cannot exhibit more than:

0.1

of resistance (+V and -V combined)

800nF of capacitance

10mF of inductance

Typically, these restrictions will yield wiring lengths of not more than

3.5m or 5.8m (1.5mm

2

and 2.5mm

2

wire respectively) without the use

of special wiring or wiring methods.

IS Pwr

Safe Area

Hazardous Area

1797 power supply

1797 power supply

1797 power supply

ACNR

Spare

IE8

OE8

IRT8

Spare

Spare

IJ2

IJ2

ACNR

OB4D

OB4D

IBN16

IBN16

IBN16

IE8

IRT8

OE8

RPA

RPFM

RPFM

IS 1797 I/O

IS 1797 I/O

IS 1797 Fiber Hub

IS Pwr
IS Pwr
IS Pwr

IS Pwr
IS Pwr
IS Pwr
IS Pwr

IS Pwr
IS Pwr
IS Pwr
IS Pwr

EEx d
/e

EEx ib

EEx d
/e

EEx ib

EEx d
/e

EEx ib

41306

Unsafe
Power
Entrance

Spare