Publication 1797-6.5.2 - February 2001

Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features 2-7

Fault Mode Select

Select whether the channel fault detection is enabled or disabled for
channels 0-3 and 4-7.

Range: 0 = disable, 1 = fault detection enabled (wire off, mV
overvoltage, RTD open). Default = 0.

Using Module Alarms

FLEX Ex I/O modules are capable of generating four alarms:

Overrange

Underrange

Fault

Cold Junction Compensation (CJC) Fault

These alarm conditions are described in general terms and as they
relate to bits on the FLEX Ex I/O module on the following pages.

Overrange Alarm

The channel overrange alarm is set if the input is greater than the
maximum temperature (thermocouple or RTD range dependent),
millivolt (+100mV) or resistance (500

) range value.

Range: 0 = normal, 1 = input overrange. Default = 0.

This alarm stays active at any value above 100% of range and is
always enabled by the module. Refer to the figure below for the
sensor dependent signal which causes this alarm to be generated.

Bits 06-07

Fault Mode bits – when a bit is set (1), fault mode is enabled for that channel.
Bit 06 corresponds to channels 0-3; bit 07 corresponds to channels 4-7.
0 = disabled
1 = enable wire-off detection