4-12 Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network

Configuration

word 1 cont.

Bits 04-05

Sensor Mode Select bits

Bit

05

04

Sensor mode select for channels 0-3

Thermocouple

0

0

CJC compensation – uses cold junction sensor

0

1

Fixed Temperature compensation – uses the value selected for reference junction

1

0

No compensation (Data is referenced to 0°C.)

1

1

Differential measurement between 2 channels

RTD

0

0

2-wire RTD no compensation

0

1

2-wire RTD with loop resistance compensation

1

0

3-wire RTD

1

1

4-wire RTD

Bits 06-07

Input Type Select

Bit

07

06

Input type selection for channels 0-3

0

0

Thermocouple

0

1

RTD

1

0

Not used

1

1

Configuration