Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual
Page 50
Advertising
![background image](/manuals/580855/50/background.png)
Publication 1797-6.5.2 - February 2001
4-12 Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network
Configuration
word 1 cont.
Bits 04-05
Sensor Mode Select bits
Bit
05
04
Sensor mode select for channels 0-3
Thermocouple
0
0
CJC compensation – uses cold junction sensor
0
1
Fixed Temperature compensation – uses the value selected for reference junction
1
0
No compensation (Data is referenced to 0°C.)
1
1
Differential measurement between 2 channels
RTD
0
0
2-wire RTD no compensation
0
1
2-wire RTD with loop resistance compensation
1
0
3-wire RTD
1
1
4-wire RTD
Bits 06-07
Input Type Select
Bit
07
06
Input type selection for channels 0-3
0
0
Thermocouple
0
1
RTD
1
0
Not used
1
1
Configuration
Word
Dec. Bits
(Octal Bits)
Description
Advertising