Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual

Page 49

Advertising
background image

Publication 1797-6.5.2 - February 2001

Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network 4-11

Configuration

Word 1

Bits 00-03

Sensor Type (Thermocouple or RTD)

RTD Type

Bit

03

02

01

00

Sensor type for channels 0 through 3

0

0

0

0

Resistance (default)

0

0

0

1

100 ohm Pt

α

= 0.00385 Euro (–200 to +870°C)

0

0

1

0

200 ohm Pt

α

= 0.00385 Euro (–200 to +400°C)

0

0

1

1

100 ohm Pt

α

= 0.003916 U.S. (–200 to +630°C)

0

1

0

0

200 ohm Pt

α

= 0.003916 U.S. (–200 to +400°C)

0

1

0

1

100 ohm Nickel (–60 to +250°C)

0

1

1

0

200 ohm Nickel (–60 to +200°C)

0

1

1

1

120 ohm Nickel (–80 to +320°C)

1

0

0

0

10 ohm Copper (–200 to +260°C)

1001 through 1111 not used

Bits 00-03

Thermocouple Type

Bit

03

02

01

00

Sensor type for channels 0 through 3

0

0

0

0

mV (default)

0

0

0

1

B

300 to 1800°C

(572 to 3272°F)

0

0

1

0

E

–270 to 1000°C

(–454 to 1832°F)

0

0

1

1

J

–210 to 1200°C

(–346 to 2192°F)

0

1

0

0

K

–270 to 1372°C

(–454 to 2502°F)

0

1

0

1

L

–200 to 800°C

(–328 to 1472°F)

0

1

1

0

N

–270 to 1300°C

(–450 to 2372°F)

0

1

1

1

R

–50 to 1768°C

(–58 to 3214°F)

1

0

0

0

S

–50 to 1768°C

(–58 to 3214°F)

1

0

0

1

T

–270 to 400°C

(–454 to 752°F)

1010 through 1111 not used

Configuration

Word

Dec. Bits

(Octal Bits)

Description

Advertising