Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual

Page 48

Advertising
background image

Publication 1797-6.5.2 - February 2001

4-10 Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network

Configuration

Word

Dec. Bits

(Octal Bits)

Description

Configuration

Word 0

Bits 00-02

Input Filter Cutoff bits

Bit

02

01

00

Definition

0

0

0

Hardware filtering only (default filtering)

0

0

1

40Hz

(25ms)

0

1

0

10Hz

(100ms)

0

1

1

4Hz

(250ms)

1

0

0

2Hz

(500ms)

1

0

1

1Hz

(1s)

1

1

0

0.5Hz

(2s)

1

1

1

0.2Hz

(5s)

Bits 03-05

Reference Junction – used when input type is set to thermocouple and sensor mode is set to Fixed
Temperature Compensation. Sets a fixed reference junction to compensate all thermocouple channels.

Bit

05

04

03

Reference Junction

0

0

0

0°C

0

0

1

20°C

0

1

0

25°C

0

1

1

30°C

1

0

0

40°C

1

0

1

50°C

1

1

0

60°C

1

1

1

70°C

Bits 06-07

Fault Mode bits – when a bit is set (1), fault mode is enabled for that channel. Bit 06 corresponds to
channels 0-3; bit 07 corresponds to channels 4-7.
0 = disabled
1 = enable wire-off detection

Bits 08-11

(10-13)

Data format – module defaults to –4000 to 10000 in millivolt mode, and 0 to 5000 in ohms mode

Bit

11

10

09

08

Data type for channels 0-7

0

0

0

0

°C

0

0

0

1

°F

0

0

1

0

°

K

0

0

1

1

–32767 to +32767

0

1

0

0

0 to 65535

0101 through 1111 not used

Bits 12-15

(14-17)

Not used