PERFORMANCE DATA — 549B, 549C (cont)

ELECTRIC HEATING CAPACITIES — 549B036-120 AND 549C024-060 (cont)

*Two heater packages required to provide kW indicated.
NOTES:

1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:

Heater kW

new

= Heater kW

rated x

(unit power distribution voltage/rated heater voltage)

2

As an example:

For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW

new

= 16 kW (215/240)

2

kW

new

= 12.8 kW (rating at 215 v)

MULTIPLICATION FACTORS

NOTE: The following equation converts kW of heat energy to Btuh:
kW x 3.413 = Btuh.

EXAMPLE: 34 kW (at 230 v) heater on 208 v

= 34.0 (.751 mult factor)
= 25.5 kW capacity at 208 v.

OUTDOOR SOUND POWER (TOTAL UNIT)

UNIT
549B

VOLTAGE

(60 Hz)

ACCESSORY

kW

ACCESSORY

HEATER

PART NUMBER

CRHEATER---A00

ACCESSORY SINGLE

POINT BOX PART NO.

CRSINGLE---A00

090

(7

1

/

2

Tons)

208/230/240

(3 phase)

7.8/ 9.6/10.4

117

007

12.0/14.7/16.0

110

007

18.6/22.8/24.8

111

009

24.0/29.4/32.0

112

009

31.8/39.0/42.4*

112,117

013

460/480

(3 phase)

12.8/13.9

116

006

15.2/16.5

113

006

25.6/27.8

114

008

30.4/33.0

115

008

38.4/41.7*

114,116

102

(8

1

/

2

Tons)

208/230/240

(3 phase)

7.8/ 9.6/10.4

117

012

12.0/14.7/16.0

110

012

18.6/22.8/24.8

111

015

24.0/29.4/32.0

112

015

31.8/39.0/42.4*

112,117

017

460/480

(3 phase)

12.8/13.9

116

011

15.2/16.5

113

011

25.6/27.8

114

014

30.4/33.0

115

014

38.4/41.7*

114,116

016

120

(10 Tons)

208/230/240

(3 phase)

7.8/ 9.6/10.4

117

012

12.0/14.7/16.0

110

012

24.0/29.4/32.0

112

015

31.8/39.0/42.4*

112,117

017

37.6/46.2/50.0*

112,110

017

460/480

(3 phase)

15.2/16.5

113

011

25.6/27.8

114

014

30.4/33.0

115

014

38.4/41.7*

114,116

016

46.0/50.0*

115,113

016

HEATER RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694

0.751

0.918

1.000

480

0.626

0.840

0.918

1.000

600

0.840

0.918

1.000

549B,

549C

ARI

RATING

(decibels)

OCTAVE BANDS; Lw (A)

63

125

250

500

1000 2000 4000 8000

024,036,048

76

50.8 63.4 62.2 65.9

69.2

65.9

63.0

56.5

060,072

80

57.6 70.2 66.9 71.7

74.7

72.2

67.8

62.4

090

82

62.3 69.3 71.5 74.7

76.2

72.9

68.7

61.5

102

84

64.6 71.1 73.3 76.9

77.6

73.7

70.6

63.7

120

84

64.6 71.1 73.3 76.9

77.6

73.7

70.6

63.7

ARI

Air Conditioning and Refrigeration Institute

Lw (A) — Unit A — Weighted Sound Power Level

549B

, 549

C

Advertising
This manual is related to the following products: