Cooling capacities – Bryant 549B User Manual

Page 82

Advertising
background image

82

PERFORMANCE DATA — 549B, 549C

COOLING CAPACITIES

549B036 (3 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

900/0.12

1200/0.15

1500/0.18

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

41.2

37.8

34.4

42.9

39.6

36.3

43.6

40.6

37.5

SHC

19.8

24.5

28.8

21.5

27.6

32.9

22.5

30.1

36.3

kW

2.11

2.08

2.05

2.12

2.10

2.07

2.12

2.10

2.08

85

TC

39.9

36.5

33.1

41.9

38.2

34.9

42.5

39.2

36.1

SHC

19.4

24.0

28.2

21.2

27.2

32.4

22.6

29.8

35.9

kW

2.36

2.34

2.31

2.38

2.35

2.33

2.38

2.36

2.35

95

TC

38.6

35.0

31.7

40.4

36.7

33.4

41.3

37.6

34.8

SHC

18.9

23.4

27.4

20.8

26.6

31.6

22.4

29.2

34.7

kW

2.65

2.62

2.58

2.66

2.63

2.61

2.67

2.64

2.63

105

TC

37.1

33.2

30.0

38.7

35.0

31.5

39.3

36.0

33.2

SHC

18.3

22.7

26.6

20.3

26.1

30.7

21.7

29.0

33.2

kW

2.96

2.92

2.88

2.98

2.95

2.90

2.97

2.96

2.93

115

TC

35.1

31.4

28.0

36.7

32.8

29.7

37.7

33.8

31.6

SHC

17.6

21.9

25.6

19.7

25.2

29.6

21.5

28.1

31.6

kW

3.29

3.25

3.20

3.31

3.27

3.23

3.32

3.29

3.26

125

TC

33.0

29.0

25.7

34.4

30.6

27.8

35.4

31.5

29.8

SHC

16.9

21.0

24.5

19.0

24.3

27.8

20.9

27.1

29.7

kW

3.65

3.59

3.53

3.68

3.62

3.57

3.69

3.64

3.61

549B048 (4 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

1200/0.1

1600/0.12

2000/0.15

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

51.0

48.9

43.9

52.3

50.2

46.0

53.7

51.5

48.1

SHC

24.1

33.1

40.3

26.0

37.0

44.2

27.8

40.9

48.0

kW

2.65

2.64

2.60

2.66

2.65

2.61

2.67

2.66

2.63

85

TC

48.9

47.1

41.9

50.7

48.4

44.2

52.6

49.8

46.6

SHC

22.9

32.2

40.2

25.4

36.4

43.4

27.9

40.6

46.6

kW

2.99

2.98

2.94

3.01

3.00

2.96

3.03

3.01

2.99

95

TC

47.1

45.1

39.2

49.0

46.3

42.1

50.8

47.6

44.9

SHC

22.3

31.5

39.2

24.9

35.6

42.1

27.4

39.8

44.9

kW

3.37

3.37

3.31

3.40

3.38

3.34

3.42

3.39

3.37

105

TC

44.9

42.9

37.5

46.8

44.1

40.3

48.7

45.4

43.2

SHC

21.3

30.7

37.5

24.1

34.8

40.3

26.9

39.0

43.1

kW

3.79

3.78

3.71

3.82

3.80

3.75

3.84

3.81

3.79

115

TC

42.9

40.8

35.2

44.6

41.9

38.3

46.3

43.0

41.3

SHC

20.4

30.1

35.2

23.3

34.0

38.3

26.1

37.9

41.3

kW

4.24

4.23

4.15

4.26

4.24

4.19

4.29

4.25

4.23

125

TC

40.9

38.2

32.9

42.2

39.3

36.1

43.5

40.5

39.3

SHC

19.8

29.1

32.9

22.4

33.0

36.1

25.1

36.9

39.3

kW

4.72

4.70

4.62

4.73

4.71

4.66

4.74

4.72

4.71

549B060 (5 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

1500/0.17

1750/0.25

2000/0.31

2500/0.42

Indoor Entering Air — Ewb (F)

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

75

TC

70.2

65.3

59.9

56.6

71.7

66.8

61.9

59.7

72.8

67.8

63.4

62.4

74.1

69.9

65.8

65.8

SHC

31.6

40.6

49.2

54.1

33.3

43.5

53.8

57.0

34.8

46.0

57.8

59.6

37.5

51.8

62.9

62.9

kW

3.51

3.47

3.45

3.43

3.52

3.48

3.46

3.44

3.45

3.49

3.47

3.46

3.55

3.51

3.48

3.48

85

TC

68.7

63.3

57.4

54.2

70.3

65.1

59.3

57.8

71.8

66.3

60.9

60.5

73.2

68.5

64.5

64.4

SHC

31.3

40.0

48.3

51.8

33.1

43.2

52.8

55.2

34.9

46.2

56.8

57.7

38.0

52.5

61.6

61.5

kW

3.95

3.91

3.89

3.87

3.96

3.92

3.89

3.89

3.98

3.93

3.91

3.91

4.00

3.96

3.93

3.92

95

TC

66.7

60.6

52.0

50.1

68.4

62.4

55.5

54.7

69.1

63.8

58.2

58.2

71.2

65.6

62.2

62.2

SHC

30.7

39.1

46.2

47.8

32.7

42.5

51.3

52.3

34.2

45.8

55.5

55.5

38.0

51.6

59.4

59.4

kW

4.43

4.39

4.34

4.32

4.45

4.41

4.37

4.37

4.46

4.43

4.39

4.40

4.48

4.43

4.42

4.42

105

TC

63.7

55.4

45.8

45.8

65.6

58.6

50.2

50.1

66.9

60.5

53.3

53.6

68.2

62.4

59.5

59.5

SHC

29.8

37.4

43.5

43.7

31.9

41.3

47.9

47.9

33.9

44.8

50.9

51.2

37.3

51.1

56.8

56.8

kW

4.96

4.91

4.81

4.81

4.99

4.94

4.86

4.86

5.00

4.96

4.90

4.90

5.00

4.97

4.95

4.95

115

TC

60.2

47.9

41.2

41.2

62.0

50.9

45.2

45.2

63.3

52.8

48.2

48.2

65.1

56.2

54.2

54.1

SHC

28.8

34.8

39.3

39.3

30.9

38.8

43.1

43.2

32.9

42.4

46.1

46.0

36.8

49.2

51.8

51.7

kW

5.55

5.43

5.33

5.33

5.57

5.46

5.40

5.40

5.58

5.49

5.44

5.44

5.59

5.53

5.50

5.50

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not

extrapolate.

2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering evapo-

rator coil

3. The SHC is based on 80 F edb temperature of

air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm)
from SHC.
Above 80 F edb, add (corr factor x cfm) to
SHC.
Correction Factor = 1.10 x (1 – BF) x
(edb – 80).

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x
(edb – 80).

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity

(Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature
corresponding to enthalpy of air
leaving evaporator coil (h

lwb

)

h

lwb

=

h

ewb

total capacity

(Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR

DRY-BULB TEMP (F)

79

78

77

76

75

under

75

81

82

83

84

85

over

85

Correction Factor

.05

1.04 2.07 3.11 4.14 5.18

Use

formula

shown
below.

.10

.98 1.96 2.94 3.92 4.90

.20

.87 1.74 2.62 3.49 4.36

.30

.76 1.53 2.29 3.05 3.82

549B