Cooling capacities, 542j – Bryant 549B User Manual

Page 146

Advertising
background image

146

PERFORMANCE DATA — 542J

COOLING CAPACITIES

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leaving indoor

coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering indoor coil

3. SHC is based on 80 F edb temperature of air entering indoor coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leaving indoor

coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering indoor coil

3. SHC is based on 80 F edb temperature of air entering indoor coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

542J150 (12

1

/

2

Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

3750/0.04

4500/0.05

5000/0.05

5625/0.06

6250/0.07

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

167.0

154.0

140.0

171.0

158.0

144.0

173.0

159.0

146.0

171.0

162.0

148.0

173.0

161.0

151.0

SHC

79.6

100.0

120.0

85.0

108.0

131.0

87.5

114.0

138.0

94.5

120.0

146.0

97.7

127.0

150.0

kW

10.00

9.77

9.50

10.10

9.87

9.61

10.20

9.93

9.68

10.20

10.00

9.74

10.20

10.00

9.80

85

TC

160.0

148.0

133.0

164.0

151.0

137.0

167.0

154.0

140.0

168.0

155.0

143.0

166.0

157.0

146.0

SHC

77.6

98.9

118.0

82.0

107.0

129.0

86.1

113.0

136.0

89.6

118.0

142.0

95.3

125.0

146.0

kW

11.10

10.80

10.40

11.20

10.90

10.60

11.30

11.00

10.70

11.30

11.00

10.80

11.30

11.10

10.80

95

TC

155.0

141.0

127.0

157.0

144.0

131.0

160.0

146.0

133.0

161.0

149.0

137.0

163.0

149.0

140.0

SHC

76.1

96.3

115.0

80.3

105.0

126.0

84.4

110.0

132.0

86.5

117.0

137.0

91.7

121.0

140.0

kW

12.20

11.80

11.40

12.20

11.90

11.50

12.40

12.00

11.60

12.40

12.10

11.80

12.50

12.10

11.90

105

TC

147.0

133.0

120.0

150.0

137.0

124.0

152.0

138.0

127.0

153.0

140.0

131.0

154.0

141.0

134.0

SHC

73.6

93.3

112.0

78.5

102.0

123.0

81.6

108.0

127.0

85.1

114.0

131.0

88.6

120.0

134.0

kW

13.20

12.70

12.30

13.30

12.90

12.50

13.40

13.00

12.60

13.50

13.10

12.80

13.50

13.10

12.90

115

TC

140.0

126.0

112.0

141.0

129.0

118.0

144.0

130.0

121.0

144.0

131.0

125.0

146.0

133.0

128.0

SHC

71.4

90.3

109.0

75.1

99.1

117.0

78.9

104.0

121.0

81.9

110.0

125.0

87.0

117.0

128.0

kW

14.20

13.70

13.20

14.30

13.90

13.50

14.40

14.00

13.70

14.50

14.00

13.90

14.60

14.10

14.00

125

TC

131.0

118.0

105.0

134.0

120.0

111.0

135.0

122.0

115.0

137.0

123.0

118.0

136.0

124.0

121.0

SHC

68.1

87.6

105.0

73.5

96.4

111.0

75.7

102.0

115.0

80.7

108.0

118.0

83.4

113.0

121.0

kW

15.20

14.70

14.10

15.40

14.90

14.50

15.40

14.90

14.70

15.60

15.00

14.90

15.60

15.10

15.00

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh)
TC

Gross Total Capacity (1000 Btuh)

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

542J180 (15 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

4500/0.06

5250/0.08

6000/0.10

6750/0.10

7500/0.12

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

210.0

192.0

173.4

216.0

196.6

178.4

220.0

202.0

182.2

222.0

204.0

185.6

224.0

206.0

190.2

SHC

100.6

125.2

148.2

106.0

134.0

160.6

110.6

143.0

172.2

115.0

151.2

183.2

120.2

158.2

190.0

kW

13.58

13.12

12.66

13.76

13.28

12.84

13.88

13.44

12.98

13.96

13.52

13.10

14.02

13.60

13.26

85

TC

202.0

183.0

164.4

208.0

187.8

169.0

212.0

191.4

172.8

212.0

194.0

177.2

214.0

195.8

182.2

SHC

98.0

121.8

144.2

103.8

131.2

156.4

109.0

140.0

168.6

112.0

148.0

177.0

116.2

155.6

182.2

kW

14.86

14.32

13.78

15.08

14.52

13.98

15.22

14.66

14.14

15.26

14.78

14.30

15.34

14.86

14.50

95

TC

192.4

173.2

155.0

196.2

177.8

159.2

200.0

180.8

163.4

202.0

183.4

169.0

204.0

185.4

174.2

SHC

94.8

118.0

140.0

100.2

127.4

152.6

105.6

136.4

163.4

110.6

144.8

169.0

114.2

153.2

173.8

kW

16.16

15.52

14.88

16.32

15.72

15.10

16.48

15.88

15.30

16.62

16.00

15.54

16.64

16.12

15.76

105

TC

182.0

163.0

145.0

186.4

167.0

149.4

188.6

170.0

155.4

191.0

172.2

160.8

193.0

173.8

165.2

SHC

91.0

114.2

135.2

96.8

123.6

147.6

101.8

132.6

155.2

107.2

141.2

160.6

112.2

149.6

165.2

kW

17.36

16.64

15.92

17.58

16.86

16.16

17.70

17.04

16.48

17.84

17.18

16.74

17.94

17.28

16.96

115

TC

171.2

152.4

134.8

175.0

156.2

140.6

177.8

158.8

146.8

179.4

160.8

152.2

179.6

162.2

156.4

SHC

87.4

110.2

130.8

92.6

119.4

140.6

98.8

128.2

146.8

103.6

136.8

151.8

107.2

144.6

156.2

kW

18.54

17.72

16.90

18.76

17.94

17.24

18.94

18.12

17.60

19.02

18.28

17.90

19.04

18.38

18.16

125

TC

159.4

141.2

125.0

162.8

143.8

132.0

165.6

147.0

137.8

166.6

148.8

143.0

168.2

150.0

146.8

SHC

83.6

105.8

125.0

89.0

115.0

131.8

94.4

123.6

137.8

99.8

132.2

142.8

105.0

139.6

146.6

kW

19.64

18.74

17.88

19.86

19.00

18.34

20.00

19.12

18.72

20.20

19.28

19.00

20.20

19.40

19.28

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh)
TC

Gross Total Capacity (1000 Btuh)

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

5

42J

Advertising
This manual is related to the following products: