GUIDE SPECIFICATIONS — 542J150,180 (cont)

J. Operating Characteristics:

1. Unit shall be capable of starting and running at 125 F

ambient outdoor temperature, meeting maximum
load criteria of ARI Standard 210/240 or 360 at
+ 10% voltage.

2. Compressor with standard controls shall be capable

of operation down to 40 F (in cooling mode) ambient
outdoor temperature.

3. Compressor with standard controls shall be capable

of operation down to –20 F (in heating mode) ambi-
ent outdoor temperature.

4. Unit shall be capable of simultaneous heating duty

and defrost cycle operation when using accessory
electric heaters.

K. Electrical Requirements:

All unit power wiring shall enter unit cabinet at a single
factory-predrilled location.

L. Motors:

1. Compressor motors shall be cooled by refrigerant

gas passing through motor windings and shall have
line break thermal and current overload protection.

2. Indoor-fan motor shall have permanently lubricated

bearings and inherent automatic-reset thermal over-
load protection.

3. Totally enclosed outdoor-fan motor shall have

permanently lubricated bearings, and inherent
automatic-reset thermal overload protection.

M. Special Features:

Certain features are not applicable when the features
designated * are specified. For assistance in amending
the specifications, contact your local Bryant Sales Office.

1. Roof Curbs (Horizontal and Vertical):

a. Formed galvanized steel with wood nailer strip

and shall be capable of supporting entire unit
weight.

b. Permits installation and securing of ductwork to

curb prior to mounting unit on the curb.

2. Horizontal Adapter Roof Curb:

Includes factory-assembled adapter and duct.

NOTE: Power exhaust and barometric relief must be
mounted in the return ductwork when used in con-
junction with this accessory.

* 3. Integrated Economizers:

a. Integrated integral modulating type capable of

simultaneous economizer and compressor
operation.

b. Available as a factory-installed option and accom-

modates vertical or horizontal return air configura-
tions. (Available as a field-installed accessory for
dedicated horizontal and/or vertical supply return
configurations.)

c. Includes all hardware and controls to provide

cooling with outdoor air.

d. Equipped with low-leakage dampers, not to

exceed 2% leakage at 1 in. wg pressure
differential.

e. Capable of introducing up to 100% outdoor air.

f.

EconoMi$erIV and EconoMi$er2 shall be
equipped with a barometric relief damper.

g. Designed to close damper(s) during loss-of-

power situations with spring return built into
motor.

h. Dry bulb outdoor-air temperature sensor shall be

provided as standard. Outdoor air sensor set
point is adjustable and shall range from 40 to
100 F. For the EconoMi$erIV, the return air sen-
sor, indoor humidity sensor, and outdoor humidity
sensor shall be provided as field-installed acces-
sories to provide enthalpy control, differential
enthalpy control, and differential dry bulb temper-
ature control. For the EconoMi$er2, the enthalpy,
differential temperature (adjustable), and differen-
tial enthalpy control shall be provided as field-
installed accessories.

i. The EconoMi$erIV and EconoMi$er2 shall have a

gear-driven parallel blade design.

j. EconoMi$erIV microprocessor control shall pro-

vide control of internal building pressure through
its accessory power exhaust function. Factory set
at 100%, with a range of 0% to 100%.

k. EconoMi$er2 shall be capable of control from a

4 to 20 mA signal through optional 4 to 20 mA
design without microprocessor control (required
for third party control interface).

l. EconoMi$erIV Microprocessor Occupied Mini-

mum Damper Position Setting maintains the mini-
mum airflow into the building during occupied
period providing design ventilation rate for full
occupancy (damper position during heating). A
remote potentiometer may be used to override
the set point.

m. EconoMi$erIV Microprocessor Unoccupied Mini-

mum Damper Position Setting — The
EconoMi$erIV dampers shall be completely
closed when the unit is in the occupied mode.

n. EconoMi$er2 Microprocessor Maximum Damper

Position Setting — Setting the maximum position
of the damper prevents the introduction of large
amounts of hot or cold air into the space. This
position is intended to satisfy the base minimum
ventilation rate.

o. EconoMi$erIV Microprocessor IAQ/DCV control

modulates the outdoor-air damper to provide
ventilation based on the optional 2 to 10 vdc CO

2

sensor input.

p. Compressor lockout sensor (opens at 35 F,

closes at 50 F).

q. Actuator shall be direct coupled to economizer

gear, eliminating linkage arms and rods.

r. Control LEDs:

1) When the outdoor-air damper is capable of

providing free cooling, the “Free Cool” LED
shall illuminate.

2) The IAQ LED indicates when the module is on

the DCV mode.

3) The EXH LED indicates when the exhaust fan

contact is closed.

s. Remote Minimum Position Control — A field-

installed accessory remote potentiometer shall
allow the outdoor-air damper to be opened or
closed beyond the minimum position in the occu-
pied mode for modified ventilation.

4. Barometric Relief Damper:

a. Package shall include damper, seals, hardware,

and hoods to relieve excess internal pressure.

b. Damper shall close due to gravity upon unit

shutdown.