PERFORMANCE DATA — 548F (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leav-

ing indoor coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering indoor

coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

INSTANTANEOUS AND INTEGRATED HEATING RATINGS

LEGEND

NOTES:

1.

indicates integrated ratings.

2. Integrated capacity is maximum (instantaneous) capacity less the

effect of frost on the outdoor coil and the heat required to defrost it.

548F120 (10 TONS)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

2800/0.11

3750/0.16

4100/0.18

4700/0.21

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

127.4

120.4

110.6

134.2

126.2

116.2

135.6

127.4

117.8

137.0

129.0

120.6

SHC

60.0

76.4

91.0

66.2

86.0

104.4

67.8

89.0

108.8

70.2

93.4

115.6

kW

8.30

8.18

7.88

8.54

8.34

8.04

8.60

8.36

8.10

8.64

8.38

8.20

85

TC

124.6

116.2

106.4

131.0

122.0

112.4

132.4

123.6

114.0

133.8

126.0

116.4

SHC

59.2

74.6

89.4

65.4

84.8

103.6

67.4

88.4

107.4

70.0

94.2

112.8

kW

9.24

9.04

8.74

9.50

9.24

8.98

9.54

9.28

9.02

9.60

9.36

9.08

95

TC

121.8

112.0

102.2

126.2

117.4

107.4

127.8

119.0

109.4

130.0

121.2

112.6

SHC

58.4

73.2

87.4

63.8

83.4

101.0

66.0

87.2

104.8

69.6

93.4

110.2

kW

10.34

10.04

9.66

10.46

10.18

9.90

10.52

10.26

9.96

10.62

10.36

10.08

105

TC

116.9

107.2

97.6

122.4

112.4

102.8

123.6

113.8

105.0

124.6

115.6

108.4

SHC

56.6

71.4

85.4

63.0

82.0

98.4

65.0

85.8

101.8

67.8

91.4

106.2

kW

11.38

11.08

10.66

11.64

11.28

10.90

11.68

11.32

11.00

11.68

11.38

11.16

115

TC

112.0

102.0

92.8

116.6

107.0

98.0

118.0

108.2

100.2

120.0

110.0

103.8

SHC

55.0

69.6

83.2

61.2

80.2

95.2

63.6

84.2

98.0

67.4

90.2

101.8

kW

12.58

12.18

11.74

12.78

11.42

12.00

12.84

12.48

12.12

12.96

12.56

12.30

125

TC

106.4

96.8

87.8

110.4

101.2

93.6

111.6

102.2

95.8

113.6

103.8

99.0

SHC

53.2

67.4

80.8

59.2

78.4

91.4

61.4

82.2

94.0

65.4

88.0

97.2

kW

13.84

13.36

12.90

13.96

13.62

13.22

14.02

13.68

13.34

14.14

13.76

13.54

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

Ldb — Leaving Dry-Bulb
Lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

548F036

Return

Air

(F db)

Cfm

(Standard

Air)

Air Temperature Entering Outdoor Coil (F)

0

10

17

30

40

47

50

60

55

900

Cap.

15.4

13.1

19.2

17.6

21.7

19.8

27.4

24.0

31.9

31.9

35.3

35.3

36.9

36.9

41.4

41.4

kW

2.25

2.44

2.57

2.86

3.10

3.29

3.38

3.64

1200

Cap.

15.9

13.5

19.4

17.8

22.5

20.5

28.3

24.8

32.9

32.9

35.8

35.8

37.0

37.0

40.1

40.1

kW

2.24

2.40

2.54

2.80

3.02

3.15

3.21

3.35

1500

Cap.

16.2

13.8

19.8

18.2

22.9

20.9

28.8

25.2

33.1

33.1

35.3

35.3

36.5

36.5

38.6

38.6

kW

2.23

2.38

2.52

2.76

2.94

3.03

3.08

3.17

70

900

Cap.

13.2

11.2

17.1

15.7

20.0

18.2

25.4

22.2

29.8

29.8

33.2

33.2

34.7

34.7

40.1

40.1

kW

2.29

2.50

2.67

2.98

3.24

3.45

3.55

3.91

1200

Cap.

13.7

11.6

17.7

16.3

20.3

18.5

26.3

23.1

30.8

30.8

34.4

34.4

36.0

36.0

40.9

40.9

kW

2.28

2.49

2.62

2.93

3.17

3.36

3.45

3.72

1500

Cap.

14.0

11.9

18.1

16.6

20.7

18.9

26.9

23.6

31.6

31.6

35.1

35.1

36.9

36.9

40.2

40.2

kW

2.27

2.47

2.60

2.89

3.12

3.30

3.38

3.54

80

900

Cap.

11.5

9.8

15.5

14.2

18.4

16.8

23.7

20.8

28.1

28.1

31.7

31.7

33.2

33.2

38.5

38.5

kW

2.30

2.54

2.71

3.04

3.32

3.55

3.65

4.03

1200

Cap.

12.0

10.2

16.2

14.8

19.2

17.5

24.7

21.6

29.3

29.3

33.0

33.0

34.5

34.5

40.2

40.2

kW

2.30

2.52

2.69

2.99

3.26

3.47

3.56

3.91

1500

Cap.

12.3

10.5

16.6

15.2

19.7

18.0

25.4

22.3

30.1

30.1

33.7

33.7

35.3

35.3

39.2

39.2

kW

2.29

2.51

2.68

2.97

3.22

3.41

3.50

3.70

Cap. — Heating Capacity (1000 Btuh) (includes indoor-fan motor heat)
db

dry bulb

kW

Total Power Input (includes compressor motor power input,

outdoor-fan motor input, and indoor-fan motor input)

548F

Advertising
This manual is related to the following products: