PERFORMANCE DATA — 549B, 549C (cont)

COOLING CAPACITIES (cont)

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leav-

ing indoor coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering indoor coil

3. SHC is based on 80 F edb temperature of air entering indoor coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

549C060 (5 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

1500/0.05

1750/.05

2000/.07

2500/.08

Indoor Entering Air — Ewb (F)

57

62

67

72

57

62

67

72

57

62

67

72

57

62

67

72

75

TC

56.2

59.2

65

70.3

59.5

61.3

66.9

71.5

62.2

62.9

68.2

72.9

66.1

66.1

70

74.1

SHC

54

49.5

41.1

32.3

57.1

54.2

44.4

33.8

59.8

58.4

47.4

35.6

63.5

63.5

53.3

38.4

kW

3.17

3.19

3.19

3.22

3.18

3.18

3.2

3.23

3.19

3.19

3.21

3.24

3.2

3.2

3.22

3.25

85

TC

53.3

56

62.6

68.5

57.2

58.4

64.5

69.9

59.9

60.1

66

70.9

64.1

64.1

67.8

72.6

SHC

51.2

48.3

40.4

31.8

55

53.1

43.8

33.6

57.6

57.2

47.1

35.3

61.6

61.6

53.2

38.6

kW

3.59

3.6

3.62

3.64

3.61

3.61

3.63

3.65

3.61

3.61

3.63

3.66

3.62

3.62

3.64

3.67

95

TC

49.1

50.5

59.4

65.8

53.6

53.7

61.3

67.7

56.8

56.8

62.7

68.7

61.5

61.5

64.8

70.5

SHC

47.1

46.1

39.3

30.9

51.6

51.1

42.7

33.1

54.7

54.6

46.1

34.8

59.1

59.1

52.6

38.6

kW

4.02

4.03

4.08

4.1

4.05

4.05

4.09

4.12

4.08

4.07

4.1

4.12

4.09

4.09

4.11

4.14

105

TC

44.7

44.6

52.9

62.4

48.8

48.9

55.4

64.2

51.5

51.5

58

65.6

57.8

57.8

60.8

67.3

SHC

42.9

42.9

37

29.9

46.9

47

40.8

32.1

49.5

49.5

44.6

34.1

55.6

55.6

51.5

37.9

kW

4.49

4.49

4.56

4.61

4.53

4.53

4.58

4.63

4.55

4.55

4.6

4.64

4.6

4.6

4.62

4.64

115

TC

39.9

40

45.2

56.4

43.9

43.9

47.2

59.5

46

46.2

49.8

61.4

52

51.9

52.6

63.3

SHC

38.4

38.4

34.3

28.1

42.2

42.2

38

30.7

44.3

44.4

41.9

33

50

50

48.8

37.1

kW

4.98

4.98

5.06

5.16

5.05

5.05

5.08

5.18

5.07

5.07

5.11

5.2

5.13

5.13

5.13

5.21

125

TC

35.9

35.9

38.4

49

38.6

38.5

39.7

50.9

41.1

41

41.3

52.8

45.1

45.2

45.3

55.6

SHC

34.5

34.5

32.1

25.8

37.1

37.1

35.5

28.1

39.5

39.5

39

30.5

43.4

43.5

43.6

35

kW

5.53

5.53

5.57

5.7

5.58

5.58

5.59

5.72

5.62

5.62

5.62

5.74

5.68

5.67

5.68

5.77

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Gross Sensible Heat Capacity (1000 Btuh)
TC

Gross Total Capacity (1000 Btuh)

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

549B

, 549

C