Cooling capacities (cont) – Bryant 549B User Manual

Page 83

Advertising
background image

83

PERFORMANCE DATA — 549B, 549C (cont)

COOLING CAPACITIES (cont)

549B072 (6 Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

1800/0.06

2100/0.066

2400/0.071

3000/0.088

Indoor Entering Air — Ewb (F)

72

67

62

57

72

67

62

57

72

67

62

57

72

67

62

57

75

TC

83.2

77.6 71.6 67.9

84.7

79.8 73.6

71.5

85.9 81.0

75.0 74.3 88.4

82.9 78.4 78.3

SHC 39.7

50.4 60.6 66.6

41.6

54.3 65.9

70.1

43.4 57.6

70.6 72.8 47.2

63.9 76.9 76.8

kW

4.90

4.78 4.69 4.63

4.94

4.84 4.71

4.69

4.97 4.86

4.74 4.73 5.04

4.91 4.81 4.81

85

TC

81.5

75.5 69.0 64.8

83.2

77.3 71.1

69.4

84.5 78.5

72.7 72.2 86.2

80.8 76.5 76.5

SHC 39.2

49.8 59.6 63.6

41.4

53.5 65.0

68.0

43.3 56.9

69.7 70.8 47.1

64.1 75.0 75.0

kW

5.45

5.34 5.23 5.16

5.49

5.36 5.27

5.23

5.52 5.38

5.29 5.27 5.57

5.45 5.36 5.36

95

TC

78.8

72.5 64.1 61.8

80.9

74.5 67.0

66.1

82.0 76.0

69.9 69.9 83.7

78.1 74.2 74.1

SHC 38.4

48.6 57.4 60.6

40.8

52.6 63.2

64.8

42.8 56.4

68.3 68.5 46.8

63.7 72.7 72.7

kW

6.03

5.91 5.79 5.73

6.09

5.96 5.84

5.82

6.11

6.00

5.89 5.89 6.16

6.05 5.96 5.96

105

TC

76.2

69.5 58.6 57.8

77.9

71.3 63.4

63.1

79.3 72.7

67.2 67.2 81.1

74.5 71.3 71.2

SHC 37.6

47.4 55.0 56.6

39.9

51.4 61.4

61.9

42.2 55.3

65.9 65.9 46.5

62.5 69.9 69.9

kW

6.69

6.56 6.40 6.38

6.73

6.61 6.45

6.44

6.77 6.64

6.51 6.51 6.82

6.67 6.57 6.57

115

TC

72.5

65.1 54.8 54.7

74.3

67.8 58.6

58.6

75.6 69.1

63.2 63.2 77.3

70.9 68.4 68.4

SHC 36.3

45.8 53.2 53.6

38.7

50.2 57.4

57.5

41.1 54.0

62.0 62.0 45.5

61.3 67.1 67.1

kW

7.37

7.24 7.08 7.07

7.43

7.30 7.16

7.16

7.48 7.34

7.21 7.21 7.52

7.38 7.32 7.32

549B090 (7

1

/

2

Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

2250/0.12

3000/0.15

3750/0.18

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

97.6

92.5

84.3

100.8

95.6

89.9

101.6

97.8

91.7

SHC

47.7

61.0

72.7

51.5

67.3

83.8

55.0

74.4

89.7

kW

5.80

5.76

5.73

5.86

5.78

5.78

5.86

5.82

5.73

85

TC

97.2

89.9

79.8

100.0

94.1

86.7

102.4

96.0

89.9

SHC

48.1

60.2

70.5

51.7

68.1

82.4

55.8

74.1

89.3

kW

6.61

6.50

6.43

6.65

6.56

6.62

6.69

6.58

6.50

95

TC

94.4

86.9

75.0

98.2

91.3

81.8

99.6

93.7

87.3

SHC

47.3

59.2

68.1

51.7

67.5

79.8

55.0

74.8

87.3

kW

7.43

7.37

7.19

7.50

7.41

7.30

7.50

7.43

7.35

105

TC

91.7

82.2

70.7

94.8

87.3

76.6

97.0

90.1

83.4

SHC

46.3

57.4

65.9

50.9

66.3

76.4

54.8

74.1

83.4

kW

8.37

8.22

8.04

8.39

8.33

8.15

8.44

8.35

8.26

115

TC

87.7

77.4

66.9

91.7

81.6

72.5

93.9

85.3

78.8

SHC

44.9

55.4

64.0

50.3

64.2

72.5

55.0

72.5

78.6

kW

9.33

9.16

8.98

9.44

9.27

9.11

9.48

9.33

9.22

125

TC

83.6

73.3

66.7

87.1

76.0

69.1

89.5

79.0

74.4

SHC

43.6

53.9

63.8

48.7

62.0

69.1

53.7

70.1

74.4

kW

10.38

10.16

9.94

10.49

10.27

10.14

10.53

10.36

10.25

549B102 (8

1

/

2

Tons)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

2550/0.03

3400/0.04

4250/0.05

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

116.4

105.6

94.8

118.9

110.4

99.4

120.4

112.9

104.3

SHC

55.7

69.2

82.0

58.6

79.7

95.8

61.6

89.2

104.2

kW

6.01

5.89

5.8

6.04

5.97

5.87

6.07

6.01

5.93

85

TC

117.6

102.1

91.1

121.0

106.7

95.6

117.5

109.3

101.3

SHC

58.4

67.9

80.4

64.1

78.6

93.9

61.0

88.4

101.2

kW

6.47

6.72

6.61

6.52

6.80

6.69

6.91

6.85

6.77

95

TC

113.7

98.0

86.1

117.4

102.3

91.3

113.4

104.7

97.9

SHC

57.4

66.5

78.2

63.5

77.2

91.1

59.9

87.2

97.8

kW

7.34

7.63

7.49

7.40

7.72

7.60

7.82

7.77

7.69

105

TC

109.8

93.0

78.7

113.2

97.3

85.9

108.9

99.9

93.7

SHC

56.2

64.6

75.0

62.4

75.5

85.9

58.7

85.5

93.6

kW

8.28

8.59

8.42

8.36

8.71

8.57

8.81

8.74

8.68

115

TC

100.2

86.4

72.7

104.5

90.0

80.8

106.0

93.2

88.0

SHC

50.4

62.1

71.9

57.2

73.0

80.8

63.4

83.2

88.0

kW

9.79

9.60

9.40

9.91

9.71

9.59

9.95

9.79

9.71

125

TC

94.0

76.6

63.1

98.8

80.1

68.1

101.0

84.4

75.1

SHC

48.3

58.5

63.1

55.4

69.2

68.1

61.9

79.8

75.1

kW

10.91

10.65

10.45

11.03

10.78

10.61

11.1

10.86

10.73

Standard Ratings

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not

extrapolate.

2. The following formulas may be used:

Where: h

ewb

= Enthalpy of air entering

evaporator coil

3. The SHC is based on 80 F edb temperature

of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm)
from SHC.
Above 80 F edb, add (corr factor x cfm) to
SHC.
Correction Factor = 1.10 x (1 – BF) x
(edb – 80).

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x
(edb – 80).

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh)

Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

=

t

edb

sensible capacity

(Btuh)

1.10 x cfm

t

lwb

=

Wet-bulb temperature
corresponding to enthalpy
of air leaving evaporator
coil (h

lwb

)

h

lwb

=

h

ewb

total capacity

(Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR

DRY-BULB TEMP (F)

79

78

77

76

75

under

75

81

82

83

84

85

over

85

Correction Factor

.05

1.04 2.07 3.11 4.14 5.18

Use

formula

shown
below.

.10

.98 1.96 2.94 3.92 4.90

.20

.87 1.74 2.62 3.49 4.36

.30

.76 1.53 2.29 3.05 3.82

549