PHYSICAL DATA

548F036-072

LEGEND

*Weight of 14-in. roof curb.

†Single phase/three phase.
NOTE: The 548F units have a loss-of-charge switch located in the liquid line.

UNIT SIZE 548F

036

048

060

072

NOMINAL CAPACITY (tons)

3

4

5

6

OPERATING WEIGHT (lb)

Unit

500

520

550

590

Economizer

EconoMi$erIV or EconoMi$er2

50

50

50

50

Roof Curb*

115

115

115

115

COMPRESSOR

Hermetic

Quantity

1

1

1

1

Oil (oz)

45

54

50

54

REFRIGERANT TYPE

R-22

Operating Charge (lb-oz)

Circuit 1

5-1

6-0

8-0

11-2

Circuit 2

OUTDOOR COIL

3

/

8

-in. OD Enhanced Copper Tubes, Aluminum Lanced Fins, Fixed Orifice Metering Device

Rows...Fins/in.

1...17

1...17

2...17

2...17

Total Face Area (sq ft)

10.31

14.58

12.25

16.53

OUTDOOR FAN

Propeller Type

Nominal Cfm

4000

4000

4000

4000

Quantity...Diameter (in.)

1...22.0

1...22.0

1...22.0

1...22.0

Motor Hp...Rpm

1

/

4

...1100

1

/

4

...1100

1

/

4

...1100

1

/

4

...1100

Watts Input (Total)

325

325

325

325

INDOOR COIL

3

/

8

-in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Fixed Orifice Metering Device

Rows...Fins/in.

2...15

2...15

3...15

3...15

Total Face Area (sq ft)

4.2

4.2

5.5

5.5

INDOOR FAN

Centrifugal Type

Quantity...Size (in.)

Std

1...10 x 10

1...10 x 10

1...11 x 10

1...10 x 10

Alt

1...10 x 10

1...10 x 10

1...10 x 10

High-Static

1...10 x 10

1...10 x 10

1...10 x 10

1...10 x 10

Type Drive

Std

Direct

Direct

Direct

Belt

Alt

Belt

Belt

Belt

High-Static

Belt

Belt

Belt

Belt

Nominal Cfm

1200

1600

2000

2400

Maximum Continuous Bhp

Std

.34

.75

1.20

2.40

Alt

1.00

1.00

1.30/2.40†

High-Static

2.40

2.40

2.90

2.90

Motor Frame Size

Std

48

48

48

56

Alt

48

48

56

High-Static

56

56

56

56

Nominal Rpm High/Low

Std

860/800

1075/970

1075/970

Alt

1620

1620

1725

High-Static

1725

1725

1725

1725

Fan Rpm Range

Std

1070-1460

Alt

760-1000

770-1175

878-1192

High-Static

1075-1455

1075-1455

1300-1685

1300-1685

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

2.8/3.8

Alt

1.9/2.9

1.9/2.9

2.4/3.4

High-Static

2.8/3.8

2.8/3.8

3.4/4.4

3.4/4.4

Nominal Motor Shaft Diameter (in.)

Std

1

/

2

1

/

2

1

/

2

5

/

8

Alt

1

/

2

1

/

2

5

/

8

High-Static

5

/

8

5

/

8

5

/

8

5

/

8

Fan Pulley Pitch Diameter (in.)

Std

4.5

Alt

4.5

4.0

4.5

High-Static

4.5

4.5

4.5

4.5

Belt, Quantity...Type...Length (in.)

Std

1...A...40

Alt

1...A...34

1...A...34

1...A...39

High-Static

1...A...39

1...A...39

1...A...40

1...A...40

Pulley Center Line Distance (in.)

Std

14.7-15.5

Alt

10.0-12.4

10.0-12.4

14.7-15.5

High-Static

10.0-12.4

10.0-12.4

14.7-15.5

14.7-15.5

Speed Change per Full Turn of

Movable Pulley Flange (rpm)

Std

80

Alt

48

70

80

High-Static

65

65

60

60

Movable Pulley Maximum Full Turns

From Closed Position

Std

5

Alt

5

5

6

High-Static

6

6

5

5

Factory Setting

Std

3

Alt

3

3

3

High-Static

3

1

/

2

3

1

/

2

3

1

/

2

3

1

/

2

Factory Speed Setting (rpm)

Std

1225

Alt

856

932

1035

High-Static

1233

1233

1416

1416

Fan Shaft Diameter at Pulley (in.)

5

/

8

5

/

8

5

/

8

5

/

8

HIGH-PRESSURE SWITCH (psig)

Standard Compressor Internal Relief (Differential)

450 ± 50

Cutout

428

Reset (Auto.)

320

LOSS-OF-CHARGE SWITCH (psig)

Cutout

7 ± 3

Reset (Auto.)

22 ± 7

FREEZE-PROTECTION THERMOSTAT (F)

Opens

30 ± 5

Closes

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable. Quantity and size depend on options selected.

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

Bhp

Brake Horsepower

548