PERFORMANCE DATA — 548F (cont)

INDOOR-FAN MOTOR PERFORMANCE — 548F036-120 UNITS

LEGEND

BHP — Brake Horsepower

*Extensive motor and electrical testing on these units ensures that the full horse-

power range of the motors can be utilized with confidence. Using your fan
motors up to the horsepower ratings shown in this table will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be affected.

†Single-phase/three-phase.

NOTES:

1. All indoor-fan motors 5 hp and larger meet the minimum efficiency require-

ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.

2. High-static motor not available on single-phase units.

UNIT
548F

INDOOR-FAN

MOTOR

UNIT

VOLTAGE

MAXIMUM ACCEPTABLE

CONTINUOUS BHP*

MAXIMUM ACCEPTABLE

OPERATING WATTS

MAXIMUM

AMP DRAW

MOTOR

EFFICIENCY (%)

036

Standard

208/230

0.34

440

2.8

75

460

1.3

575

1.3

Alternate

208/230

1.00

1000

4.9

460

2.1

575

2.1

High Static

208/230

2.40

2120

6.0

460

3.0

575

3.0

048

Standard

208/230

0.75

850

3.5

75

460

1.8

575

1.8

Alternate

208/230

1.00

1000

4.9

460

2.1

575

2.1

High Static

208/230

2.40

2120

6.0

460

3.0

575

3.0

060

Standard

208/230

1.20

1340

5.9

74

460

3.2

575

3.2

Alternate

208/230

1.30/2.40†

2120

7.6/6.0†

460

3.0

575

3.0

High Static

208/230

2.90

2562

8.6

460

3.9

575

3.9

072

Standard

208/230

2.40

2120

6.0

84

460

3.0

575

3.0

High Static

208/230

2.90

2562

8.6

460

3.9

575

3.9

090

Standard,

Alternate

208/230

2.40

2120

6.0

80

460

3.0

575

3.0

High Static

208/230

3.70

3313

11.7

460

5.5

575

5.5

120

Standard

208/230

2.40

2120

6.0

80

460

3.0

575

3.0

Alternate

208/230

2.90

2615

8.6

460

3.9

575

3.9

High Static

208/230

5.25

4400

17.3

460

8.5

575

8.5

548

F

Advertising