120

ELECTRICAL DATA — 549B (cont)

549B036-120 STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET (cont)

LEGEND

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If

power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.

†Heaters are field installed only.

**Fuse or HACR circuit breaker.

††Electrical disconnect cannot be used if electric heater is installed.
NOTES:

1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%

IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 549B060 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. In all cases, the MOCP for the
power exhaust should be 15 amps per NEC.

UNIT
549B

NOMINAL

VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

(each)

IFM

ELECTRIC HEAT*

POWER SUPPLY

MINIMUM UNIT

DISCONNECT

SIZE

Min

Max

RLA

LRA

FLA

FLA

kW†

FLA

MCA

MOCP

FLA

LRA

090

(7

1

/

2

Tons)

208/230-3-60

187

254

12.4

88.0

1.4

7.5

7.8/10.4

12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4

21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0

38.2/ 38.2
65.3/ 69.5
79.8/ 86.3

102.7/112.8
121.5/134.5
148.6/165.7

40/ 40**
70/ 70**
80/ 90

110/125

125/150
150/175

40/ 40
65/ 69
79/ 85

100/109

117/129

142/158

242/242
264/267
275/281††
294/302††
309/319††
330/344††

460-3-60

414

508

6.4

44.0

0.7

3.4

13.9
16.5
27.8
33.0
41.7

16.7
19.8
33.4
39.7
50.2

19.2
40.1
44.0
61.0
68.8
82.0

20**
45**
45**

70
70
90

20
39
43
59
66
78

121
138
141
155
161
171

102

(8

1

/

2

Tons)

208/230-3-60

187

254

13.9

105

1.4

7.5

41.3/ 41.3

45/ 45**

43/43

276/276

7.8/10.4

21.7/ 25.0

68.4/ 72.5

70/ 80**

68/72

298/301

12.0/16.0

33.3/ 38.5

82.9/ 89.4

90/ 90

82/88

309/315††

18.6/24.8

51.6/ 59.7

105.8/115.9

110/125

103/112

328/336††

24.0/32.0

66.6/ 77.0

124.5/137.5

125/150

120/132

343/353††

31.8/42.4

88.3/102.0

151.7/168.8

175/175

145/161

364/378††

460-3-60

414

508

7.9

55.0

0.7

3.4

22.3

25**

23

143

13.9

16.7

43.2

45**

43

160

16.5

19.8

47.0

50**

46

163

27.8

33.4

64.0

70

62

177

33.0

39.7

71.9

80

69

183

41.7

50.2

85.0

90

81

193

120

(10 Tons)

208/230-3-60

187

254

19.3

123.0

1.4

10.6

7.8/10.4

12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0

21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0

104.4/120.3

56.8/ 56.8
84.0/ 88.1
98.5/105.0

140.1/153.1
167.2/184.3
187.3/177.1

60/ 60**
90/ 90

100/110

150/175
175/200
200/200

60/ 60
85/ 89
98/104

136/148
161/177
180/198

337/337
358/362††
370/375††
403/414††
425/439††
441/457††

460-3-60

414

508

10.0

62.0

0.7

4.8

16.5
27.8
33.0
41.7
50.0

19.8
33.4
39.7
50.2
60.1

28.7
53.5
70.5
78.3
91.5
88.8

30**
60**
80
80

100
100

30
53
69
76
88
99

170
189
203
209

220††
230††

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor-Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor-Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.68

N/A

15

CRPWREXH022A01

3.4

N/A

1.32

15

CRPWREXH023A01

N/A

1.4

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

0.7

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

7
457

549B

, 549

C