Bryant 549B User Manual

Page 155

Advertising
background image

155

TYPICAL WIRING SCHEMATIC — 542J (cont)

LEGEND

C

Contactor, Compressor

CAP

Capacitor

CB

Circuit Breaker

CH

Crankcase Heater

CLO

Compressor Lockout

COMP

Compressor Motor

DB

Defrost Board

DFT

Defrost Thermostat

FL

Freeze Protection Limit Switch

FPT

Freeze Protection Thermostat

FU

Fuse

GND

Ground

HC

Heater Contactor (Electric Heater)

HPS

High-Pressure Switch

HR

Heater Relay

HTR

Heater

IFC

Indoor-Fan Contactor

IFCB

Indoor Fan Circuit Breaker

IFM

Indoor-Fan Motor

IP

Internal Protection

LPS

Low-Pressure/Loss-of-Charge Switch

LS

Limit Switch

OFM

Outdoor Fan Motor

OP

Overload Protection

QT

Quadruple Terminal

RVR

Reversing Valve

RVS

Reversing Valve Solenoid

TB

Terminal Block

TRAN — Transformer

Field Splice

Terminal (Marked)

Marked Wire

Terminal (Unmarked)
Terminal Block

Splice

Splice Marked

Factory Wiring

Field Control Wiring

Field Power Wiring

Accessory or Optional Wiring

To indicate common potential only.
Not to represent wiring.

LEGEND

DCV — Demand Controlled Ventilation
IAQ

Indoor Air Quality

LALS — Low Temperature Compressor

Lockout Switch

OAT — Outdoor-Air Temperature
POT — Potentiometer

Potentiometer Defaults Settings:
Power Exhaust

Middle

Minimum Pos.

Fully Closed

DCV Max.

Middle

DCV Set

Middle

Enthalpy

C Setting

NOTES:

1. 620 ohm, 1 watt 5% resistor should be removed only when using differential

enthalpy or dry bulb.

2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power

supply, it cannot have the secondary of the transformer grounded.

3. For field-installed remote minimum position POT, remove black wire jumper

between P and P1 and set control minimum position POT to the minimum
position.

EconoMi$erIV Wiring — 542J150,180

a48-7992