548f – Bryant 549B User Manual

Page 57

Advertising
background image

57

ELECTRICAL DATA — 548F (cont)

548F036-120 (UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET) (cont)

LEGEND

*Heaters are field installed only.

†Used to determine minimum disconnect size per NEC.

**Heater capacity (kW) is based on heater voltage of 208 v, 240 v and 480 v. If

power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.

††Fuse or HACR circuit breaker.

***Optional disconnect switch is unavailable.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%.
Use the following formula to determine the percent of voltage
imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 548F060 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. In all cases, the MOCP for the
power exhaust should be 15 amps per NEC.

UNIT
548F

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

FLA

IFM

FLA

ELECTRIC HEAT*

POWER SUPPLY

DISCONNECT

SIZE†

Min

Max

RLA

LRA

Nominal

kW**

FLA

MCA

MOCP

FLA

LRA

072

(6 Tons)

208/230-3-60

STD

187

254

22.7

146.0

1.4

5.8

35.6/ 35.6

40/ 40††

34/ 34

190/190

4.9/ 6.5

13.6/15.6

52.6/ 55.1

60/ 60††

50/ 52

204/206

7.9/10.5

21.9/25.3

63.0/ 67.2

70/ 70

60/ 63

212/215

12.0/16.0

33.3/38.5

77.2/ 83.7

80/ 90

73/ 79

223/229

15.8/21.0

43.9/50.5

90.5/ 98.7

100/100

85/ 92

234/241***

19.9/26.5

55.2/63.8

104.6/115.3

110/125

98/108

245/254***

HIGH-

STATIC

187

254

22.7

146.0

1.4

7.5

37.3/ 37.3

40/ 40††

36/ 36

209/209

4.9/ 6.5

13.6/15.6

54.3/ 56.8

60/ 60††

52/ 54

223/225

7.9/10.5

21.9/25.3

64.7/ 68.9

70/ 70

62/ 65

231/234

12.0/16.0

33.3/38.5

78.9/ 85.4

80/ 90

75/ 81

242/248***

15.8/21.0

43.9/50.5

92.2/100.4

100/110

87/ 94

253/260***

19.9/26.5

55.2/63.8

106.3/117.0

110/125

100/110

264/273***

460-3-60

STD

414

508

11.4

73.0

0.7

2.6

17.6

20††

17

95

6.0

7.2

26.6

30††

25

102

11.5

13.8

34.8

35††

33

109

14.0

16.8

38.6

40††

36

112

23.0

27.7

52.2

60††

49

123

25.5

30.7

55.9

60††

52

126

HIGH-

STATIC

414

508

11.4

73.0

0.7

3.4

18.4

20††

18

105

6.0

7.2

27.4

30††

26

112

11.5

13.8

35.6

40††

34

118

14.0

16.8

39.4

40††

37

121

23.0

27.7

53.0

60††

50

132

25.5

30.7

56.7

60††

53

135

575-3-60

STD

518

632

9.1

58.4

0.7

2.6

14.0

15††

14

76

HIGH-

STATIC

518

632

9.1

58.4

0.7

3.4

14.7

15††

14

84

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

=

457

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.68

N/A

15

CRPWREXH022A01

3.4

N/A

1.32

15

CRPWREXH023A01

N/A

1.4

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

0.7

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

7
457

548F

Advertising