SELECTION PROCEDURE (WITH 549B048 EXAMPLE)

I DETERMINE COOLING AND HEATING REQUIRE-

MENTS AT DESIGN CONDITIONS:

Given:

Required Cooling Capacity (TC) . . . . . . . . . . 38,000 Btuh

Sensible Heat Capacity (SHC). . . . . . . . . . . . 24,000 Btuh

Required Heating Capacity . . . . . . . . . . . . . . 35,000 Btuh

Outdoor Entering-Air Temperature. . . . . . . . . . . . . . . 95 F

Outdoor-Air Winter Design Temperature . . . . . . . . . . . 0° F

Indoor-Air Winter Design Temperature . . . . . . . . . . . 70 F

Indoor Entering-Air

Temperature . . . . . . . . 80 F edb (entering air, dry bulb),

67 F ewb (entering air, wet bulb)

Indoor-Air Quantity. . . . . . . . . . . . . . . . . . . . . . . 1600 cfm

External Static Pressure. . . . . . . . . . . . . . . . . . 0.45 in. wg

Electrical Characteristics (V-Ph-Hz). . . . . . . . . . . 230-3-60

II SELECT UNIT BASED ON REQUIRED COOLING

CAPACITY.

Enter Cooling Capacities table at outdoor entering temper-
ature of 95 F, indoor air entering at 1600 cfm and
67 F ewb. The 549B048 unit will provide a total cooling
capacity of 46,300 Btuh and a sensible heat capacity of
35,600 Btuh.

For indoor-air temperature other than 80 F edb, calculate
sensible heat capacity correction, as required, using the
formula found in Note 3 following the cooling capacities
tables.

NOTE: Unit ratings are gross capacities and do not
include the effect of indoor-fan motor heat. To calculate
net capacities, see Step V.

III SELECT ELECTRIC HEAT.

Enter the Instantaneous and Integrated Heating Ratings
table at 1600 cfm. At 70 F return indoor air and 0° F air
entering outdoor coil, the integrated heating capacity is
22,400 Btuh. (Select integrated heating capacity value
since deductions for outdoor-coil frost and defrosting have
already been made. No correction is required.)

The required heating capacity is 35,000 Btuh. Therefore,
12,600 Btuh (35,000 – 22,400) additional electric heat is
required.

Determine additional electric heat capacity in kW.

Enter the Electric Heating Capacities table for 549B048 at
208/230, 3 phase. The 6.5-kW heater at 240 v most
closely satisfies the heating required. To calculate kW at
230 v, use the Multiplication Factors table.

6.5 kW x .92 = 5.98 kW

6.5 kW x .92 x 3413 = 20,410 Btuh

Total unit heating capacity is 42,810 Btuh (22,400 +
20,410).

IV DETERMINE FAN SPEED AND POWER REQUIRE-

MENTS AT DESIGN CONDITIONS.

Before entering Fan Performance tables, calculate the
total static pressure required based on unit components.
From the given and the Pressure Drop tables, find:

Enter the Fan Performance table for 549B048 vertical dis-
charge at 1600 cfm and .61 in. wg static pressure. The
bhp is 0.79 and the watts are 781. The rpm is 997. The
standard motor will adequately handle job requirements.

V DETERMINE NET CAPACITIES.

Capacities are gross and do not include the effect of
indoor-fan motor (IFM) heat.

Determine net cooling capacity as follows:

Integrated heating capacity is maximum (instantaneous)
capacity less the effect of frost on the outdoor coil and the
heat required to defrost it. Therefore, net capacity is equal
to 42,810 Btuh, the total heating capacity determined in
Step III.

12,600 Btuh

= 3.7 kW of heat required.

3413 Btuh/kW

External static pressure

.45 in. wg

EconoMi$erIV

.07 in. wg

Electric heat

.09 in. wg

Total static pressure

.61 in. wg

Net capacity = Total capacity – IFM heat

= 46,300 Btuh – (781 Watts x 3.413

Btuh/Watts)

= 46,300 Btuh – 2665 Btuh
= 43,635

Net sensible capacity

= 35,600 Btuh – 2665 Btuh
= 32,935 Btuh

549