Bryant 549B User Manual

Page 75

Advertising
background image

75

PHYSICAL DATA — 549C024-060

LEGEND

*Single phase/three phase.

UNIT SIZE 549C

024

036

048

060

NOMINAL CAPACITY (tons)

2

3

4

5

OPERATING WEIGHT (lb)

Unit

550

550

560

630

EconoMi$erIV

50

50

50

50

Roof Curb

115

115

115

115

COMPRESSOR

Scroll

Quantity

1

1

1

1

Oil (oz)

80

42

42

53

REFRIGERANT TYPE

R–22

Operating Charge (lb)

5.2

12.0

12.0

18.3

OUTDOOR FAN

Propeller Type

Quantity...Diameter (in.)

1...22

1...22

1...22

1...22

Nominal Cfm

3000

3500

3500

3500

Motor Hp...Rpm

1

/

8

...760

1

/

8

...825

1

/

8

...825

1

/

4

...1100

OUTDOOR COIL

Enhanced Copper Tubes, Aluminum Fins, Fixed Orifice Metering Device

Rows...Fins/in.

1...17

2...17

2...17

2...17

Total Face Area (sq ft)

14.58

16.53

16.53

21.25

INDOOR FAN

Centrifugal Type

Quantity...Size (in.)

Std

1...10 x 10

1...10 x 10

1...10 x 10

1...10 x 10

High-Static

1...10 x 10

1...10 x 10

1...10 x 10

Type Drive

Std

Belt

Belt

Belt

Belt

High-Static

Belt

Belt

Belt

Nominal Cfm

800

1200

1600

2000

Maximum Continuous Bhp

Std

0.58

1.20

1.20

1.30/2.40*

High-Static

2.40

2.40

2.90

Motor Frame Size

Std

39

48

48

56

High-Static

56

56

56

Nominal Rpm High/Low

Std

1620

1620

1620

1725

High-Static

1725

1725

1725

Fan Rpm Range

Std

639-936

680-1044

770-1185

1035-1460

High-Static

1075-1455

1075-1455

1300-1685

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

1.9/2.9

1.9/2.9

1.9/2.9

2.4/3.4

High-Static

2.8/3.8

2.8/3.8

3.4/4.4

Nominal Motor Shaft Diameter (in.)

Std

1

/

2

1

/

2

1

/

2

5

/

8

High-Static

5

/

8

5

/

8

5

/

8

Fan Pulley Pitch Diameter (in.)

Std

5.2

4.5

4.0

4.5

High-Static

4.5

4.5

4.5

Belt, Quantity...Type...Length (in.)

Std

1...A...36

1...A...34

1...A...34

1...A...39

High-Static

1...A...39

1...A...39

1...A...40

Pulley Center Line Distance (in.)

Std

10.0-12.4

10.0-12.4

10.0-12.4

14.7-15.5

High-Static

10.0-12.4

10.0-12.4

14.7-15.5

Speed Change per Full Turn of

Movable Pulley Flange (rpm)

Std

60

48

70

80

High-Static

65

65

60

Movable Pulley Maximum Full Turns

From Closed Position

Std

5

5

5

6

High-Static

6

6

5

Factory Setting

Std

3

3

3

3

High-Static

3

1

/

2

3

1

/

2

3

1

/

2

Factory Speed Setting (rpm)

Std

758

826

936

1249

High-Static

1233

1233

1416

Fan Shaft Diameter at Pulley (in.)

5

/

8

5

/

8

5

/

8

5

/

8

INDOOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Fixed Orifice Metering Device

Rows...Fins/in.

2...15

2...15

3...15

4...15

Total Face Area (sq ft)

5.5

5.5

5.5

7.33

HIGH–PRESSURE SWITCH (psig)

Standard Compressor Internal Relief

625

Cutout

428

Reset (Auto.)

320

LOSS OF CHARGE

(Liquid Line) (psig)

Cutout

7 ± 3

Reset (Auto.)

22 ± 5

FREEZE PROTECTION THERMOSTAT

Opens (F)

30

Closes (F)

45

OUTDOOR-AIR INLET SCREENS

Cleanable

Screen quantity and size varies with option selected

RETURN–AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

Bhp — Brake Horsepower

549

B, 5

49C

Advertising
This manual is related to the following products: