PERFORMANCE DATA — 542J (cont)

FAN PERFORMANCE — VERTICAL DISCHARGE UNITS (cont)

LEGEND

*Standard drive range is 817 to 1038 rpm. Alternate drive range is 1082

to 1303. Other rpms may require a field-supplied drive.

NOTES:

1. Maximum continuous bhp is 5.90 and maximum continuous watts

are 5180. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.

2. Fan performance is identical for horizontal discharge applications

using horizontal adapter curb (CRRFCURB013A00).

3. See this page for General Fan Performance notes.

GENERAL NOTES FOR FAN PERFORMANCE TABLES

1. Extensive motor and electrical testing on these units ensures that

the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. For additional information on motor performance,
refer to Indoor-Fan Motor Performance table on page 150.

2. Values include losses for filters, unit casing, and wet coils. See

page 151 for accessory/FIOP static pressure information.

3. Use of a field-supplied motor may affect wire sizing. Contact your

Bryant representative for details.

4. Interpolation is permissible. Do not extrapolate.

542J180 (15 TONS)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

4500

584

717

0.8

695

952

1.1

798

1205

1.3

893

1483

1.7

984

1786

2.0

4800

609

839

0.9

717

1085

1.2

815

1346

1.5

907

1630

1.8

994

1938

2.2

5100

634

971

1.1

738

1229

1.4

833

1500

1.7

921

1791

2.0

1006

2104

2.4

5400

660

1118

1.3

760

1389

1.6

852

1669

1.9

937

1968

2.2

1019

2286

2.6

5700

687

1284

1.4

783

1566

1.8

873

1858

2.1

956

2165

2.4

1034

2490

2.8

6000

712

1458

1.6

805

1752

2.0

892

2055

2.3

973

2371

2.7

1049

2703

3.0

6300

736

1644

1.8

826

1952

2.2

911

2265

2.5

990

2591

2.9

1064

2930

3.3

6600

763

1856

2.1

851

2176

2.4

933

2502

2.8

1010

2837

3.2

1082

3186

3.6

6900

788

2078

2.3

873

2410

2.7

954

2747

3.1

1029

3093

3.5

1099

3451

3.9

7200

813

2316

2.6

896

2662

3.0

975

3011

3.4

1048

3367

3.8

1117

3734

4.2

7500

841

2584

2.9

921

2943

3.3

998

3304

3.7

1070

3672

4.1

1137

4049

4.5

542J180 (15 TONS)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

4500

1070

2113

2.4

1151

2458

2.8

1229

2819

3.2

1302

3194

3.6

4800

1078

2269

2.5

1157

2620

2.9

1233

2990

3.3

1306

3374

3.8

5100

1086

2439

2.7

1164

2795

3.1

1238

3170

3.5

5400

1097

2626

2.9

1172

2986

3.3

1245

3366

3.8

5700

1110

2835

3.2

1183

3200

3.6

1253

3584

4.0

6000

1122

3053

3.4

1193

3422

3.8

1262

3810

4.3

6300

1135

3286

3.7

1204

3660

4.1

1271

4052

4.5

6600

1151

3549

4.0

1218

3928

4.4

1283

4325

4.8

6900

1167

3821

4.3

1232

4207

4.7

1295

4608

5.2

7200

1183

4113

4.6

1246

4505

5.0

7500

1202

4437

5.0

1264

4837

5.4

Bhp

Brake Horsepower Input to Fan

Watts — Input Watts to Motor