548 f – Bryant 549B User Manual

Page 64

Advertising
background image

64

ELECTRICAL DATA — 548F (cont)

548F036-120 (UNITS WITH ELECTRICAL CONVENIENCE OUTLET) (cont)

LEGEND

*Heaters are field installed only.

†Used to determine minimum disconnect size per NEC.

**Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v, and 575 v. If power

distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

††Fuse or HACR circuit breaker.

***Optional disconnect switch is unavailable.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer

to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust MCA and
MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the new
MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 548F060 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change. The
MOCP in this example is 40 amps and the MCA New is below 40; therefore the MOCP is
acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP to the next larger
size. In all cases, the MOCP for the power exhaust should be 15 amps per NEC.

UNIT
548F

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

FLA

IFM

FLA

ELECTRIC

HEAT*

POWER SUPPLY

DISCONNECT

SIZE†

Min

Max

RLA

LRA

Nominal

kW**

FLA

MCA

MOCP

FLA

LRA

120

(10 Tons)

460-3-60

STD

414

508

8.6

59.6

0.7

2.6

25.5

30††

27

145

16.5

19.8

50.3

60††

50

165

27.8

33.4

67.3

70

65

178

33.0

39.7

75.2

80

73

185

41.7

50.2

88.3

90

85

195***

50.0

60.1

85.6

90

96

205***

ALT

414

508

8.6

59.6

0.7

3.4

26.3

30††

28

185

16.5

19.8

51.1

60††

51

204

27.8

33.4

68.1

70

66

218

33.0

39.7

76.0

80

73

224

41.7

50.2

89.1

90

86

235***

50.0

60.1

86.4

90

97

245***

HIGH-STATIC

414

508

8.6

59.6

0.7

7.4

30.3

35††

32

179

16.5

19.8

55.1

60††

55

198

27.8

33.4

72.1

80

71

212

33.0

39.7

80.0

80

78

218

41.7

50.2

93.1

100

90

229***

50.0

60.1

90.4

100

102

239***

575-3-60

STD

518

632

6.9

49.4

0.7

2.6

20.5

25††

22

120

17.0

17.1

41.8

45††

41

137

34.0

34.1

63.1

70

61

154

51.0

51.2

71.7

80

80

171***

ALT

518

632

6.9

49.4

0.7

3.4

21.1

25††

22

151

17.0

17.1

42.5

45††

42

168

34.0

34.1

63.7

70

62

185

51.0

51.2

72.3

80

81

202***

HIGH-STATIC

518

632

6.9

49.4

0.7

7.4

24.3

25††

26

146

17.0

17.1

45.7

50††

46

163

34.0

34.1

66.9

70

65

180

51.0

51.2

75.5

80

85

198***

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.68

N/A

15

CRPWREXH022A01

3.4

N/A

1.32

15

CRPWREXH023A01

N/A

1.4

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

0.7

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

7
457

548

F