PERFORMANCE DATA — 548F (cont)

COOLING CAPACITIES (cont)

548F072 (6 TONS)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

1800/0.10

2400/0.13

3000/0.19

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

75

TC

81.1

77.6

72.1

84.0

80.3

75.2

84.2

81.1

77.8

SHC

36.2

46.9

57.0

39.1

52.4

65.4

40.8

56.2

72.2

kW

5.16

5.11

5.01

5.23

5.16

5.06

5.23

5.17

5.11

85

TC

80.7

75.8

70.0

83.9

79.3

73.4

84.1

80.8

76.2

SHC

36.1

46.5

56.4

39.7

52.9

65.2

41.6

58.3

71.9

kW

5.83

5.74

5.65

5.90

5.81

5.69

5.90

5.84

5.76

95

TC

79.3

73.0

67.3

82.0

76.7

70.8

83.0

79.1

73.5

SHC

35.8

45.4

55.3

39.3

52.3

64.3

42.2

58.9

69.7

kW

6.54

6.37

6.28

6.60

6.47

6.37

6.62

6.55

6.40

105

TC

76.0

70.6

64.3

79.6

73.4

67.9

80.7

75.5

71.3

SHC

34.6

44.8

54.1

38.8

51.2

62.9

42.0

57.6

67.8

kW

7.21

7.12

6.94

7.34

7.15

7.06

7.36

7.22

7.14

115

TC

72.7

67.5

61.1

75.8

70.6

64.7

77.9

71.8

68.5

SHC

33.6

43.7

52.7

37.6

50.7

60.9

41.5

56.4

65.2

kW

7.95

7.86

7.63

8.06

7.95

7.77

8.14

7.94

7.90

125

TC

70.1

63.9

57.6

71.8

66.9

61.6

73.5

68.6

65.4

SHC

32.9

42.4

51.2

36.4

49.5

58.4

40.2

56.1

62.3

kW

8.82

8.62

8.37

8.83

8.73

8.54

8.89

8.79

8.69

548F090 (7

1

/

2

TONS)

Temp (F)

Outdoor

Entering Air

(Edb)

Indoor Entering Air — Cfm/BF

2250/0.04

3000/0.06

3200/0.08

3750/0.11

Indoor Entering Air — Ewb (F)

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

109.8 101.4 92.2 116.2 107.0 98.0 117.6 108.8 100.2 118.8

110.4 102.4

SHC

44.2

57.4 69.4

49.6

66.0 82.0

51.8

69.8

87.0

54.0

74.0

92.0

kW

6.66

6.44

6.18

6.86

6.60

6.36

6.92

6.66

6.42

6.94

6.70

6.48

85

TC

105.2

96.4

87.0 111.4

102.2 92.6 113.0 104.0

95.0

114.6 105.8

97.6

SHC

42.8

55.6

67.6

48.4

65.0 80.0

50.8

69.0

84.4

53.4

73.8

88.8

kW

7.20

6.94

6.64

7.42

7.14

6.82

7.48

7.20

6.90

7.54

7.28

7.00

95

TC

100.6

91.0

82.0 105.6

96.2

87.4 107.2

98.0

89.8

108.6

99.6

92.8

SHC

41.6

54.0

65.8

47.0

63.2

77.8

49.4

67.4

81.4

52.0

72.2

84.6

kW

7.78

7.42

7.08

7.96

7.62

7.30

8.00

7.70

7.40

8.06

7.76

7.50

105

TC

94.8

85.4

76.8

99.8

90.2

82.2 101.4

91.6

85.0

103.2

93.2

88.0

SHC

40.0

52.2

63.8

45.6

61.6

74.6

48.2

65.8

77.6

51.2

70.4

80.4

kW

8.26

7.88

7.50

8.48

8.10

7.76

8.56

8.18

7.88

8.64

8.24

8.02

115

TC

88.8

79.9

71.4

93.4

84.0

77.6

94.8

85.4

80.0

96.0

86.6

83.0

SHC

38.4

50.4

61.6

44.2

59.8

70.6

46.6

64.0

73.2

49.4

68.6

75.8

kW

8.76

8.32

7.90

8.98

8.54

8.22

9.04

8.62

8.36

9.10

8.70

8.50

125

TC

82.6

73.8

65.8

86.6

77.4

74.4

88.0

78.8

75.0

89.2

80.0

77.6

SHC

36.8

48.6

59.2

42.2

57.8

66.2

45.2

62.0

68.6

48.2

66.6

71.0

kW

9.20

8.74

8.30

9.44

8.96

8.68

9.52

9.02

8.82

9.60

9.12

8.98

LEGEND

NOTES:

1. Direct interpolation is permissible. Do

not extrapolate.

2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corre-

sponding to enthalpy of air
leaving indoor coil (h

lwb

)

Where: h

ewb

= Enthalpy of air enter-

ing evaporator coil

3. The SHC is based on 80 F edb tem-

perature of air entering indoor coil.
Below 80 F edb, subtract (corr factor
x cfm) from SHC.
Above 80 F edb, add (corr factor x
cfm) to SHC.

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

Ldb — Leaving Dry-Bulb
Lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity

(1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

548

F

Advertising