Bryant 549B User Manual

Page 50

Advertising
background image

50

PERFORMANCE DATA — 548F (cont)

FAN RPM AT MOTOR PULLEY SETTINGS* — 548F036-120

*Approximate fan rpm shown.

†Indicates alternate motor and drive package.

**Indicates high-static motor and drive package.

††Indicates standard motor and drive package.

***Indicates alternate drive package only.

ACCESSORY/HEATER STATIC PRESSURE* (in. wg) — 548F036-072

*The static pressure must be added to external static pressure. The sum and the evaporator

entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.

ACCESSORY/HEATER STATIC PRESSURE* (in. wg) — 548F090-120

*The static pressure must be added to external static pressure. The sum and the evaporator

entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in wg) — 548F036-072

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.

ACCESSORY/FIOP STATIC PRESSURE* (in wg) — 548F090-120

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.

UNIT
548F

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

036†

1000

976

952

928

904

880

856

832

808

784

760

—

—

036**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

048†

1175

1135

1094

1054

1013

973

932

892

851

811

770

—

—

048**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

060†

1192

1166

1140

1114

1087

1061

1035

1009

983

957

930

904

878

060**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

—

—

072††

1460

1420

1380

1345

1305

1265

1225

1185

1150

1110

1070

—

—

072**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

—

—

090††

840

815

790

765

740

715

690

665

635

615

590

—

—

090***

935

910

885

860

835

810

785

760

735

710

685

—

—

090**

1080

1025

1007

988

970

952

933

915

897

878

860

—

—

120††

935

910

885

860

835

810

785

760

735

710

685

—

—

120†

1085

1060

1035

1010

985

960

935

910

885

860

835

—

—

120**

1130

1112

1087

1062

1037

1012

987

962

937

912

887

862

830

COMPONENT

CFM

900

1200

1400

1600

1800

2000

2200

2400

2600

3000

1 Heater Module

0.05

0.07

0.09

0.09

0.10

0.11

0.11

0.12

0.13

0.15

2 Heater Modules

0.15

0.16

0.16

0.16

0.17

0.17

0.17

0.18

0.18

0.19

COMPONENT

CFM

2250

2500

3000

3500

4000

4500

5000

5500

6000

6250

1 Heater Module

0.02

0.03

0.05

0.07

0.08

0.10

0.12

0.14

0.16

0.17

2 Heater Modules

0.03

0.05

0.07

0.09

0.12

0.14

0.16

0.19

0.21

0.20

COMPONENT

CFM

1250

1500

1750

2000

2250

2500

2750

3000

Vertical EconoMi$erIV and EconoMi$er2

0.045

0.065

0.08

0.12

0.145

0.175

0.22

0.255

Horizontal EconoMi$erIV and EconoMi$er2

—

—

0.1

0.125

0.15

0.18

0.225

0.275

COMPONENT

CFM

2250

2500

2750

3000

3250 3500 3750

4000

4250 4500

4750

5000

5250 6250

Vertical EconoMi$erIV and EconoMi$er2

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

—

Horizontal EconoMi$erIV and EconoMi$er2

—

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

—

—

—

548

F

Advertising
This manual is related to the following products: