PERFORMANCE DATA — 548F (cont)

FAN RPM AT MOTOR PULLEY SETTINGS* — 548F036-120

*Approximate fan rpm shown.

†Indicates alternate motor and drive package.

**Indicates high-static motor and drive package.

††Indicates standard motor and drive package.

***Indicates alternate drive package only.

ACCESSORY/HEATER STATIC PRESSURE* (in. wg) — 548F036-072

*The static pressure must be added to external static pressure. The sum and the evaporator

entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.

ACCESSORY/HEATER STATIC PRESSURE* (in. wg) — 548F090-120

*The static pressure must be added to external static pressure. The sum and the evaporator

entering-air cfm should then be used in conjunction with the Fan Performance tables to deter-
mine blower rpm and watts.

ACCESSORY/FIOP STATIC PRESSURE* (in wg) — 548F036-072

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.

ACCESSORY/FIOP STATIC PRESSURE* (in wg) — 548F090-120

LEGEND

FIOP — Factory-Installed Option

*The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.

UNIT
548F

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

036†

1000

976

952

928

904

880

856

832

808

784

760

036**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

048†

1175

1135

1094

1054

1013

973

932

892

851

811

770

048**

1455

1423

1392

1360

1328

1297

1265

1233

1202

1170

1138

1107

1075

060†

1192

1166

1140

1114

1087

1061

1035

1009

983

957

930

904

878

060**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

072††

1460

1420

1380

1345

1305

1265

1225

1185

1150

1110

1070

072**

1685

1647

1608

1570

1531

1493

1454

1416

1377

1339

1300

090††

840

815

790

765

740

715

690

665

635

615

590

090***

935

910

885

860

835

810

785

760

735

710

685

090**

1080

1025

1007

988

970

952

933

915

897

878

860

120††

935

910

885

860

835

810

785

760

735

710

685

120†

1085

1060

1035

1010

985

960

935

910

885

860

835

120**

1130

1112

1087

1062

1037

1012

987

962

937

912

887

862

830

COMPONENT

CFM

900

1200

1400

1600

1800

2000

2200

2400

2600

3000

1 Heater Module

0.05

0.07

0.09

0.09

0.10

0.11

0.11

0.12

0.13

0.15

2 Heater Modules

0.15

0.16

0.16

0.16

0.17

0.17

0.17

0.18

0.18

0.19

COMPONENT

CFM

2250

2500

3000

3500

4000

4500

5000

5500

6000

6250

1 Heater Module

0.02

0.03

0.05

0.07

0.08

0.10

0.12

0.14

0.16

0.17

2 Heater Modules

0.03

0.05

0.07

0.09

0.12

0.14

0.16

0.19

0.21

0.20

COMPONENT

CFM

1250

1500

1750

2000

2250

2500

2750

3000

Vertical EconoMi$erIV and EconoMi$er2

0.045

0.065

0.08

0.12

0.145

0.175

0.22

0.255

Horizontal EconoMi$erIV and EconoMi$er2

0.1

0.125

0.15

0.18

0.225

0.275

COMPONENT

CFM

2250

2500

2750

3000

3250 3500 3750

4000

4250 4500

4750

5000

5250 6250

Vertical EconoMi$erIV and EconoMi$er2

0.06

0.075

0.09

0.115

0.13

0.15

0.17

0.195

0.22

0.25

0.285

0.325

0.36

Horizontal EconoMi$erIV and EconoMi$er2

0.1

0.125

0.15

0.18

0.21

0.25

0.275

0.3

0.34

0.388

548

F

Advertising
This manual is related to the following products: