122

ELECTRICAL DATA — 549B (cont)

549B036-120 — STANDARD MOTOR UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)

LEGEND

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, or 480 v. If

power distribution voltage to unit varies from rated heater voltage, heater kW
will vary accordingly.

†Heaters are field installed only.

**Fuse or HACR circuit breaker.

††Electrical disconnect cannot be used if electric heater is installed.
NOTES:

1. In compliance with NEC requirements for multimotor and combination load

equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.

% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

= 457

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

% Voltage Imbalance= 100 x

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-
tact your local electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

N/A — Not available
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 549B060 unit with MCA = 35.6 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 35.6 amps + 1.6 amps = 37.2 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. In all cases, the MOCP for the
power exhaust should be 15 amps per NEC.

UNIT
549B

NOMINAL

VOLTAGE

(V-Ph-Hz)

VOLTAGE

RANGE

COMPRESSOR

(each)

OFM

(each)

IFM

ELECTRIC HEAT*

POWER SUPPLY

MINIMUM UNIT

DISCONNECT

SIZE

Min

Max

RLA

LRA

FLA

FLA

kW†

FLA

MCA

MOCP

FLA

LRA

090

(7

1

/

2

Tons)

208/230-3-60

187

254

12.4

88.0

1.4

7.5

7.8/10.4

12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4

21.7/ 25.0
33.3/ 38.5
51.6/ 59.7
66.6/ 77.0
88.3/102.0

43.0/ 43.0
70.1/ 74.3
84.6/ 91.1

107.5/117.6
126.3/139.3
153.4/170.5

45/ 45**

80/ 80
90/100

110/125
150/150
175/175

46/ 46
71/ 75
84/ 90

105/115
122/134
147/163

247/247
269/272

280/285††
298/307††
313/324††
335/349††

460-3-60

414

508

6.4

44.0

0.7

3.4

13.9
16.5
27.8
33.0
41.7

16.7
19.8
33.4
39.7
50.2

21.4
42.3
46.1
63.1
71.0
84.1

25**
45**
50**
70
80
90

23
42
46
61
68
80

123
140
143
157
163
174

102

(8

1

/

2

Tons)

208/230-3-60

187

254

13.9

105

1.4

7.5

46.1/ 46.1

50/ 50**

49/ 49

281/281

7.8/10.4

21.7/ 25.0

73.2/ 77.3

80/ 80

74/ 78

303/306

12.0/16.0

33.3/ 38.5

87.7/ 94.2

90/100

87/ 93

314/319††

18.6/24.8

51.6/ 59.7

110.6/120.7

125/125

108/118

332/341††

24.0/32.0

66.6/ 77.0

129.3/142.3

150/150

126/138

347/358††

31.8/42.4

88.3/102.0

156.5/173.6

175/175

151/166

369/383††

460-3-60

414

508

7.9

55.0

0.7

3.4

24.5

25**

26

145

13.9

16.7

45.3

50**

45

162

16.5

19.8

49.2

50**

49

165

27.8

33.4

66.2

70

64

179

33.0

39.7

74.1

80

72

185

41.7

50.2

87.2

90

84

196

120

(10 Tons)

208/230-3-60

187

254

19.3

123.0

1.4

10.6

7.8/10.4

12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0

21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.3/102.0

104.4/120.3

61.6/ 61.6
88.8/ 92.9

103.3/109.8
144.9/157.9
172.0/189.1
192.1/181.9

70/ 70
90/100

110/110

150/175
175/200
200/200

65/ 65
90/ 94

104/110
142/154
167/183
185/204

341/341
363/366††
375/380††
408/418††
430/443††
446/462††

460-3-60

414

508

10.0

62.0

0.7

4.8

16.5
27.8
33.0
41.7
50.0

19.8
33.4
39.7
50.2
60.1

30.9
55.6
72.6
80.5
93.6
91.0

35**
60**

80
90

100
100

33
55
71
78
90

102

172
191
205

211
222††
232††

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor-Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor-Fan Motor

RLA

Rated Load Amps

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

POWER EXHAUST

PART NO.

MCA

(230 v)

MCA

(460 v)

MCA

(575 v)

MOCP

(for separate

power source)

CRPWREXH021A01

N/A

0.68

N/A

15

CRPWREXH022A01

3.4

N/A

1.32

15

CRPWREXH023A01

N/A

1.4

N/A

15

CRPWREXH028A01

1.7

N/A

0.68

15

CRPWREXH029A01

N/A

0.7

N/A

15

CRPWREXH030A01

1.6

N/A

0.64

15

7
457

549B

, 549

C