Quality assurance – Bryant 549B User Manual

Page 5

Advertising
background image

5

MODEL NUMBER NOMENCLATURE — 542J150,180 UNITS

ARI* CAPACITY RATINGS

548F036-060

548F072-120

LEGEND

*Air Conditioning and Refrigeration Institute.

†Applies only to units with capacity of 60,000 Btuh or less.

**The IPLV applies only to 2-stage cooling heat pump units.

NOTES:
1. Rated in accordance with ARI Standards 210/240-95 and 270-95.
2. Ratings are net values, reflecting the effects of circulating fan heat.
3. ALL the 548F036-060 units are in compliance with ASHRAE 90.1

2001 Energy Standard for minimum SEER and EER requirements.
Refer to state and local codes or visit the following website:
http://solstice.crest.org/efficiency/bcap to determine if compliance
with this standard pertains to a given geographical area of the United
States.

4. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature
and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.
High-Temp Heating Standard: 70 F db indoor entering-air temperature
and 47 F db, 43 F wb outdoor entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor entering-air temperature
and 17 F db, 15 F wb outdoor entering-air temperature.

UNIT
548F

NOMINAL

TONS

COOLING

HEATING

(High Temp)

SOUND

RATING

(decibels)

Net Capacity

(Btuh)

SEER†

Capacity

(Btuh)

HSPF

Belt

Drive

Direct

Drive

036

3

35,600

10.20

10.00

34,400

6.7

84

048

4

46,500

10.00

9.70

46,500

7.0

80

060

5

57,000

10.00

9.90

57,000

7.5

82

UNIT
548F

NOMINAL

TONS

COOLING

HEATING

(High)

HEATING

(Low)

IPLV**

SOUND

RATING

(decibels)

Net Capacity

(Btuh)

EER

Capacity

(Btuh)

COP

Capacity

(Btuh)

COP

072

6

70,000

9.05

72,400

3.20

42,000

2.14

82

090

7

1

/

2

86,000

9.00

78,000

3.00

39,000

1.80

9.3

86

120

10

112,000

9.00

105,000

3.10

59,000

2.00

9.0

84

COP

Coefficient of Performance

db

dry bulb

EER

Energy Efficiency Ratio

HSPF — Heating Seasonal Performance Factor
IPLV

Integrated Part-Load Values

SEER — Seasonal Energy Efficiency Ratio
wb

wet bulb

Nominal Cooling Capacity
150 –
12 Tons
180 – 15 Tons

Factory-Installed Outdoor
Air Upgrade Options
C –
Economizer
H – 25% Manual Damper

542J E X 150 000 AB H B

542J – High-Efficiency Rooftop Units

Electric Heat Pumps

Voltage Designation
E –
460-3-60
P –
T –

208/230-3-60
575-3-60

Heat Type
X –
No Heat Installed

Electric Heaters
000 –
No Factory-Installed Electric Heaters

Accessory Field-Installed Electric Heaters
Available

Fan Drive Position
(Standard Motor)
B –
Standard Low-Medium

Fan Drive Static Capability

D – Alternate High Fan

Drive Static Capability

Design Series Code
AB –
Economizer Design Change

Quality Assurance

Certified to ISO 9001:2000

a50-8040

Advertising
This manual is related to the following products: