548f – Bryant 549B User Manual

Page 53

Advertising
background image

53

PERFORMANCE DATA — 548F (cont)

ELECTRIC HEATING CAPACITIES — 548F090-120

*Two heater packages required to provide kW indicated.

NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:

Heater kW new = Heater kW rated x (unit power distribution voltage/rated heater voltage)

2

As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW new = 16 kW (215/240)

2

kW new = 12.8 kW (rating at 215 v)

UNIT
548F

UNIT VOLTAGE

(60 Hz)

ACCESSORY

kW

ELECTRIC HEATER

PART NUMBER

CRHEATER---A00

SINGLE POINT BOX

PACKAGE NO.

CRSINGLE---A00

090

208/230/240

(3 phase)

7.8/ 9.6/10.4

12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0

31.8/39.0/42.4*

017
010
011
012

012 and 017

007
007
009
009
013

460/480

(3 phase)

12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0

38.4/41.7*

016
013
014
015

014 and 016

006
006
008
008
010

575

(3 phase)

17.0
34.0

018
019

006
006

120

208/230/240

(3 phase)

7.8/ 9.6/10.4

12.0/14.7/16.0
24.0/29.4/32.0

31.8/39.0/42.4*
37.6/46.2/50.0*

017
010
012

012 and 017
010 and 012

012
012
015
017
017

460/480

(3 phase)

15.2/16.5
25.6/27.8
30.4/33.0

38.4/41.7*
45.9/50.0*

013
014
015

014 and 016
013 and 015

011
014
014
016
016

575

(3 phase)

17.0
34.0
51.0*

018
019

018 and 019

011
014
016

548F

Advertising
This manual is related to the following products: