PERFORMANCE DATA — 542J (cont)

FAN RPM AT MOTOR PULLEY SETTINGS*

*Approximate fan rpm shown.

†Indicates standard motor and drive package.

**Indicates standard motor and alternate drive package.

INDOOR-FAN MOTOR PERFORMANCE — STANDARD MOTORS

LEGEND

BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors

can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.

UNIT

542J

MOTOR PULLEY TURNS OPEN

0

1

/

2

1

1

1

/

2

2

2

1

/

2

3

3

1

/

2

4

4

1

/

2

5

5

1

/

2

6

150 (208/230 V and 460 V)†

1179

1150

1121

1093

1064

1035

1006

978

949

920

891

150 (208/230 V and 460 V)**

1559

1522

1488

1455

1422

1389

1356

1323

1289

1256

1227

150 (575 V)†

1429

1403

1376

1349

1323

1296

1269

1242

1215

1188

1159

180†

1038

1023

1001

979

956

934

912

890

868

846

817

180**

1303

1288

1266

1244

1222

1199

1177

1155

1133

1111

1082

UNIT

542J

UNIT

VOLTAGE

MAXIMUM

CONTINUOUS BHP*

MAXIMUM

OPERATING WATTS*

MAXIMUM

AMP DRAW

MOTOR

EFFICIENCY

150

208/230-3-60

4.25

3775

10.5

85.8

460-3-60

4.9

85.8

575-3-60

3.45

3065

3.9

81.7

180

208/230-3-60

5.90

5180

15.8

87.5

460-3-60

7.9

87.5

575-3-60

6.0

87.5

Fan Performance Using Accessory Power Exhaust — 542J150,180

a50-4028

5

42J

Advertising
This manual is related to the following products: