Step 2: apply power, Step 3: binding the gateway and nodes, Basic setup – Banner SureCross DX80 Wireless Networks User Manual

Page 17: On the gateway

Advertising
background image

17

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

SureCross Wireless Network

Product Manual

Basic Setup

Step 2: Apply Power

1. Apply power to the Gateway by connecting the 10-30V dc cable as shown in the wiring diagram.

The Gateway begins in *RUN mode, displays the current network ID (NID), then identifies itself as a Gateway.

2. Apply power to the Node by connecting the 10-30V dc cable or the DX81 Battery Supply Module as shown.

The Node starts in *RUN mode, displays the current network ID, then identifies itself as a Node and lists the device ID. Once running,
the Node begins displays its I/O points.

Wire Color 10 to 30V dc Powered

Node

Battery Powered Node

1

Brown

+10 to 30V dc Input

2

White

3

Blue

dc common (GND)

dc common (GND)

4

Black

5

Gray

3.6 to 5.5V dc

For FlexPower devices, do not apply more than 5.5V dc to the gray wire.

RS-485

RS-232

Wire Color 10 to 30V dc Gateway,

GatewayPro, DX85*

FlexPower Gateway**

GatewayPro, DX83

Ethernet Bridge*

FlexPower Gateway**

1

Brown

+10 to 30V dc Input

+10 to 30V dc Input

+10 to 30V dc Input

+10 to 30V dc Input

2

White

RS-485 / D1 / B / +

RS-485 / D1 / B / +

RS-232 Tx

RS-232 Tx

3

Blue

dc common (GND)

dc common (GND)

dc common (GND)

dc common (GND)

4

Black

RS-485 / D0 / A / −

RS-485 / D0 / A / −

RS-232 Rx

RS-232 Rx

5

Gray

Comms grnd

3.6 to 5.5V dc

Comms grnd

3.6 to 5.5V dc

* Connecting dc power to the communication pins will cause permanent damage.
** For FlexPower devices, do not apply more than 5.5V dc to the gray wire.

Step 3: Binding the Gateway and Nodes

Binding Nodes to their Gateway ensures the Nodes only exchange data with the Gateway they are bound to. The Gateway automatically
generates a unique extended addressing, or binding, code when the Gateway enters binding mode. This code is then transmitted to all radios
within range that are also in binding mode. After a Node is bound, the Node accepts data only from the Gateway to which it is bound. The
extended addressing (binding) code defines the network, and all radios within a network must use the same code.
After binding your Nodes to the Gateway, make note of the binding code displayed under the *DVCFG menu, XADR submenu on the LCD.
Knowing the binding code prevents having to re-bind all Nodes if your Gateway is ever replaced.
To automatically bind the Gateway and its Node(s), follow these steps:

On the Gateway

Step 1. Disconnect the Gateway from its power source.
Step 2. Remove the Gateway’s top cover.
Step 3. Move DIP switch 1 to the ON position to activate Extended Addressing Mode.
Step 4. Apply power to the Gateway. The LCD shows POWER, then *RUN.
Step 5.

Advertising