Troubleshooting

Restoring Factory Default Settings

Restoring the factory default settings resets the settings for:

Parameter

Default Setting

IP Address

192.168.0.1

Root Login

root

Root Password

sxi

HTTP Port

80

Modbus Server Port

502

Telnet Port

23

EtherNet/IP Protocol

Disabled

To restore these settings, leave the device powered up and running and
follow these steps:

1. Open the DX80 GatewayPro or DX83 Ethernet Bridge housing

to access the board

2. Install the initialization (init) jumper on the pins shown
3. Wait 30 seconds
4. Remove the jumper
5. Cycle power to the device

Using the configuration Web page, verify the parameters have returned to
the factory defaults listed in the table.

Serial Communication (RS-232 or
RS-485)

The GatewayPro and Ethernet Bridge devices use jumpers to select
between RS-485 and RS-232 communications. Because all DX80
devices are RS-485 based (at this time), verify the jumpers are set
correctly. Install the four jumpers across the two top rows of pins for
RS-485 and across the bottom two rows of pins for RS-232.

Initialization pins

Communications pins