Specifications, Radio, General – Banner SureCross DX80 Wireless Networks User Manual

Page 95: Communications, Environmental

Advertising
background image

95

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

SureCross Wireless Network

Product Manual

Specifications

Range*

900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)

Transmit Power

900 MHz: 21 dBm Conducted
2.4 GHz: 18 dBm Conduced, ≤20 dBm EIRP

Spread Spectrum Technology

FHSS (Frequency Hopping Spread Spectrum)

Antenna Connector

Ext. Reverse Polarity SMA, 50 Ohms

Antenna Max Tightening Torque

0.45 N•m (4 in•lbf)

Link Timeout

Gateway: Configurable, up to 2 minutes
Node: Defined by Gateway

* With the standard 2 dB antenna. High-gain antennas are available, but the range depends on the environment and line of sight. To determine the range of your wireless
network, perform a Site Survey.

Radio

Power

+10 to 30V dc (For European applications: +10 to 24V dc, ±
10%)
FlexPower: +10 to 30V dc or 3.6 to 5.5V dc low power option
(For European applications: +10 to 24V dc, ± 10% or 3.6 to
5.5V dc low power option)
Internal battery: 3.6V dc low power option from an internal
battery

Power Consumption. Less than 1.4 W (60 mA) at 24V dc
Mounting. #10 or M5 (M5 hardware included)

M5 Fasteners Max Tightening Torque. 0.56 N•m (5 in•lbf)
Case Material. Polycarbonate
Weight. 0.26 kg (0.57 lb.)
Indicators. Two LED, bi-color
Switches. Two Push Buttons
Display. Six Character LCD
External Cable Glands. Four PG-7 type, One 1/2 NPT type
Cable Glands Max Tightening Torque. 0.56 N•m (5 in•lbf)

* For European applications, power the DX80 from a Limited Power Source as defined in EN 60950-1.

General

Interface. 2-wire RS-485
Baud Rates. 9.6k, 19.2k (default), or 38.4k

Data Format. 8 data bits, no parity, 1 stop bit
Protocol. Modbus RTU

Communications

DX80...C Models
Environmental Rating* (device case).
IEC IP20; NEMA 1
Environmental Rating* (in suitable enclosure). Class I, Division 2,
Group A, B, C, D
T4 −40 to 80° C
Operating Temperature.** −40 to +85° C (Electronics); −20 to
+80° C (LCD)
Operating Humidity. 95% max. relative (non-condensing)
Radiated Immunity. 10 V/m, 80-2700 MHz (EN61000-6-2)
Shock and Vibration. IEC 68-2-6 and IEC 68-2-7

Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz

DX80 Models
Environmental Rating.*
IEC IP67; NEMA 6
Operating Temperature.** −40 to +85° C (Electronics); −20 to
+80° C (LCD)
Operating Humidity. 95% max. relative (non-condensing)
Radiated Immunity. 10 V/m, 80-2700 MHz (EN61000-6-2)
Shock and Vibration. IEC 68-2-6 and IEC 68-2-7;

Shock: 30g, 11 millisecond half sine wave, 18 shocks;
Vibration: 0.5 mm p-p, 10 to 60 Hz

Environmental

* Please refer to the SureCross™ DX80 Wireless I/O Network product manual, Banner p/n 132607, for installation and waterproofing instructions.
** Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.

Advertising