Calculating battery life, Power solutions – Banner SureCross DX80 Wireless Networks User Manual

Page 66

Advertising
background image

66

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

SureCross Wireless Network

Product Manual

Power Solutions

DX81 Battery Supply

Module

DX80 FlexPower Node

with MINI-BEAM

Averaging Fluke meter

BWA-HW-010 Cable, FlexPower Current

Monitoring

Calculating Battery Life

To measure the current draw of a system similar to the one shown below, use Banner cable
BWA-HW-0010.
To measure,

1. Connect the cable to the FlexPower Node and the battery supply module as shown

below. The cable’s male end plugs into the FlexPower Node and the female end
plugs into the battery module.

2. Connect an averaging Fluke meter to the leads. Set the meter to read in amps, not

milliamps.

3. Turn off the Node’s LCD panel by clicking button 2 five times.
4. Allow the meter to measure the operation for at least 10 times the length of the

sample rate.

To estimate the battery life in hours, use the following equation:

Battery life (hours) =

16,000 mA Hr

average current (mA)

To estimate the battery life in years, use the following equation:

Battery life (years ) =

16,000 mA Hr

average current (mA) Ч 8736