Constant voltage during the test indicates a
“PASS” response. If the voltage changes more than
one-quarter of a volt (.25), the test indicates a
“FAIL” response.

4.

If the test indicates a “FAIL” response, refer to the
“Power Supply Integrity Test Indicating Fluctuat-
ing Voltage” flow chart on the next page to trou-
bleshoot the unit. If the test indicates a “PASS”
response, return to the “External Request to Exit
Input Not Activating prox.pad plus” flow chart
and resume your work.

5.3 Performing Power Supply Integrity Test

Chapter 5: Troubleshooting

prox.pad plus Install/Program. Manual, PPP, D4b

5-7