background image

4.3 Programming
Outputs

4.3.1 Changing the
Lock Output Time

The factory default main relay time is five (5) seconds.
Main Lock Output time can be set in one-second in-
crements from 1-255 seconds using command 11.
1.

Place the prox.pad plus unit in Program mode.
Press:

99 # Master Code * (default is 1234)

A slow blinking yellow LED indicates that the unit
is in Program mode. A steady yellow LED, in
contrast, means that errors were detected during
programming. Error states can be cleared by press-
ing the asterisk * key.

2.

Enter the new Lock Output time, in seconds (from
1 to 255). For example, to enter 10 seconds, press:

11 # 10 # 0 # **

The yellow LED continues to blink slowly.

3.

Press * to exit Program mode.

4.3.2 Assigning
Outputs

The prox.pad plus unit is equipped with four virtual
outputs and four physical outputs. The virtual outputs
consist of the Lock Output, Alarm Shunt Function,
Propped Door Output, and Forced Door Output. A
virtual output is simply an output that can be assigned
to a physical output. The physical outputs include the
Main Relay, the Aux Relay, Audio Alert #1, and Audio
Alert #2. The default output assignments are:

Lock Output is assigned to the Main Relay

Alarm Shunt Function is assigned to the Aux Relay

Forced Door Output is assigned to Audio Alert #1

Propped Door Output is assigned to Audio Alert
#2

4.3 Programming Outputs

Chapter 4: Programming

prox.pad plus Install/Program. Manual, PPP, D4b

4-17

Part No. 6105679, Rev. 1.1