4.5.2.A Programming a Transaction Dump Code

1.

Place the prox.pad plus unit in Program mode.
Press:

99 # Master Code * (default is 1234)

A slow blinking yellow LED indicates that the unit
is in Program mode. A steady yellow LED, in
contrast, means that errors were detected during
programming. Error states can be cleared by press-
ing the asterisk * key.

2.

For a LOG DUMP USER (Code Only), press:

50 # 2 # user location # code * code *

For a CARD DUMP, press:

50 # 2 # user location # ** <present card>

and then present the card at the proximity reader.
(NOTE: A Log Dump User can also be a “card
AND Code” or “Card OR Code” user.)

3.

Press * to exit Program mode.

NOTE:

Entering the programmed dump code or card

again subsequently causes the unit to send a Transac-
tion Log to the optional PDA DCD program.

4.5.2.B Printing a Transaction Log Manually

1.

Place the prox.pad plus unit in Program mode.
Press:

99 # Master Code * (default is 1234)

A slow blinking yellow LED indicates that the unit
is in Program mode. A steady yellow LED, in
contrast, means that errors were detected during
programming. Error states can be cleared by press-
ing the asterisk * key.

2.

Hold the PDA up to the prox.pad plus IR port
steadily (about one or two inches away; the IR
port is located to the right of the yellow LED) and
then press:

70 # 0 # 0 # **

Chapter 4: Programming

4.5 Using the Printing Features

4-32

prox.pad plus Install/Program. Manual, PPP, D4b

Part No. 6105679, Rev. 1.1