In systems with 2 or more stores, the correspon-
ding number of seperate menu items (Store 1 to
Store 5) is displayed instead of Store.
For each store, an individual ∆T control, a set and a
maximum temperature, the priority, a hysteresis, a rise
value, a minimum runtime and a minimum pump speed
can be adjusted.
In multi-store-systems with differing Store set / Ma-
ximum store temperatures, all stores are loaded up
to their Stset temperatures first (according to their
priority and the store sequence control). Only when
all stores have exceeded Stset will they be loaded
up to their Stmax temperatures, again according to
their priority and the store sequence control.

Store (1 / 2 / 3 / 4 / 5)

Solar / Basic settings / Store (1 / 2 / 3 / 4 / 5)

Adjustment channel Description

Adjustment range / selection Factory setting

∆Ton

Switch-on temperature difference 1.0 ... 20.0 K [2.0 ... 40.0°Ra] 6.0 K [12.0 °Ra]

∆Toff

Switch-off temperature difference 0.5 ... 19.5 K [1.0 ... 39.0°Ra] 4.0 K [8.0 °Ra]

∆Tset

Set temperature

1.5 ... 30.0 K [1.5 ... 60.0°Ra] 10.0 K [20.0 °Ra]

Stset

Store set temperature

4 ... 95 °C [40 ... 204 °F]

45 °C [114 °F]

Stmax

Maximum store temperature

4 ... 95 °C [40 ... 204 °F]

60 °C [140 °F]

Priority

Priority

1

1 ... 5
(system-dependent)

HysSt

Hysteresis maximum store
temperature

0.1 ... 10.0 K [0.2 ... 20.0°Ra] 2.0 K [4.0 °Ra]

Rise

Rise

1.0 ... 20.0 K [2.0 ... 40.0°Ra] 2.0 K [4.0 °Ra]

tmin

Minimum runtime

0 ... 300

180

Min speed.

Minimum speed

30 ... 100 %

30 %

Deactivated

Blocked for solar loading

Yes, No

No