STIEBEL ELTRON SOM 10 User Manual

Page 7

Advertising
background image

en

7

2.3

Data communication / Bus

The controller is equipped with the VBus

®

for data

transfer with and energy supply to external modules.
The connection is carried out at the two terminals
marked VBus and GND (any polarity). One or more
VBus

®

modules can be connected via this data bus,

such as:
• GA3 Large Display module /

Smart Display SD3

• AM1 Alarm module
• DL2 Datalogger
• EM Extension module
Furthermore, the controller can be connected to a
PC via the VBus

®

/ USB or VBus

®

/ LAN interface adap-

ter (not included with the SOM 10). With the Service-
Center Software (RSC), measured values can be read,
processed and visualized. The software allows easier
paramatrisation and function control of the system.

Connect the FlowRotor to the input marked Flow-
Rotor.
Connect the analog Grundfos Direct Sensors
to the inputs GDSA1 and GDSA2.

The terminals S13 to S15 can be used as either im-
pulse inputs for V40 flowmeters or as inputs for FS08
flow switches
V40 flowmeters can be connected to the terminals
S13 / V40 to S15 / V40 and GND (either polarity).
Connect the irradiation sensor CS10 to the termi-
nals CS10 and GND with correct polarity. To do so,
connect the cable marked GND to the GND com-
mon terminal block, the cable marked CS to the ter-
minal marked CS10.
The terminals marked PWM are control outputs
for high-efficiency pumps.
In the In-/Outputs menu, relays can be allocated to
the PWM outputs.

Connect the digital Grundfos Direct Sensors
to the GDSD1 and GDSD2 inputs.

Note:
For more information about accessories, see
page 80

The controller is supplied with power via a power
supply cable. The power supply of the device must be
100 ... 240 V~ (50 ... 60Hz).

The power supply connection is at the terminals:
Neutral conductor N

Conductor L

Conductor L' (L' is not connected with the power
supply cable. L' is a fused contact permanently carry-
ing voltage)
Protective grounging conductor (common termi-
nal block)

WARNING!

Electric shock!
L‘ is a fused contact permanently
carrying voltage

Î

Always disconnect the con-
troller from power supply
before opening the housing!