Depending on whether the bypass is energized by a
valve or by a second pump, a corresponding adjust-
ment can be made in the menu item Variant. Depen-
ding on the variant, different control logics are applied:
Pump:
In this version, a bypass pump is placed in front of the
collector pump.
The bypass pump is first activated when store loading
is possible. If the switch-on condition is fulfilled, the
bypass pump is switched off and the collector circuit
pump is activated.
Valve:
A bypass valve is placed into the solar circuit.
The solar heat exchanger is first bypassed when store
loading is possible. If the above-mentioned switch-on
condition is fulfilled, the bypass relay switches the coll-
ector circuit via the heat exchanger.

Variant valve:

Variant pump:

Exemplary schematics for the bypass variants

Adjustment channel Description

Adjustment range / selection

Factory setting

Collector

Collector field

system dependent

system dependent

Relay

Bypass relay

system dependent

system dependent

Variant

Variant (pump or valve logic)

pump, valve

pump

Sensor

Bypass sensor

system dependent

system dependent

∆Ton

Switch-on temperature difference

1.0 ... 20.0 K [2.0 ... 40.0 °Ra]

6.0 K [12.0 °Ra]

∆Toff

Switch-off temperature difference

0.5 ... 19.5 K [1.0 ... 39.0 °Ra]

4.0 K [8.0 °Ra]

Funct.

Activation / Deactivation

Activ., Deactivated

Activ.

Solar / Opt. functions / Add new function... / Bypass

Bypass sensor

Relay

Bypass sensor

Relay