Adjustment channel Description

Adjustment range / selection

Factory setting

Relay

Relay selection

system dependent

system dependent

Sensor top

Top sensor selection

system dependent

system dependent

Sensor base

Base sensor selection

system dependent

system dependent

TBoiler on

Boiler switch-on temperature 0 ... 94 °C [32 ... 202 °F]

45 °C [114 °F]

TBoiler off

Boiler switch-off temperature 1 ... 95 °C [34 ... 204 °F]

60 °C [140 °F]

Timer

Timer option

Yes, No

No

Timer

Timer

-

-

Days of the week

Day selection

All days, Monday ... Sunday, Continue -

Timer

Time frame adjustment

00:00 ... 23:45

-

Funct.

Activation / Deactivation

Activ., Deactivated

Deactivated

Arrangement / Opt. functions / Add new function... / Boiler loading

Error relay

The error relay function can be used to operate a re-
lay in the case of an error. Thus, e. g. a signaling device
can be connected to signal errors.
If the error relay function is activated, the allocated
relay will be energized when a sensor fault occurs. If
the flow rate monitoring function is activated, the er-
ror relay will additionally energized in the case of a
flow rate error.

Adjustment channel Description

Adjustment range / selection

Factory setting

Relay

Relay selection

system dependent

system dependent

Funct.

Activation / Deactivation

Activ., Deactivated

Deactivated

Arrangement / Opt. functions / Add new function... / Error relay