11 hqm – STIEBEL ELTRON SOM 10 User Manual

Page 67

Advertising
background image

en

67

adjustment channel Description

Adjustment range / selection

Factory setting

Demand

Demand relay selection

system dependent

system dependent

Loading pump

Loading pump option

Yes, No

No

Relay

Loading pump relay selection

system dependent

system dependent

Overrun time

Overrun option

Yes, No

No

Duration

Overrun time

1 ... 10 min

1 min

Mode

Operating mode

Boiler, Therm.

Therm.

Sensor 1

Sensor 1

system dependent

system dependent

Sensor 2

Sensor 2 (only if Mode = Boiler) system dependent

system dependent

Ton

Switch-on temperature

0 ... 94 °C [32 ... 202 °F]

40 °C [104 °F]

Toff

Switch-off temperature

1 ... 95 °C [34 ... 204 °F]

45 °C [114 °F]

Timer

Timer option

Yes, No

No

Timer

Timer

-

-

Days of the week

Day selection

All days, Monday ... Sunday,
Continue

-

Timer

Time frame adjustment

00:00 ... 23:45

-

Funct.

Activation / Deactivation

Activ., Deactivated

Deactivated

Heating / Opt. functions / Add new function... / DHW heating

11 HQM

In the HQM menu, up to seven internal heat quantity
measurements can be activated and adjusted.
By selecting the menu item New HQM, a new heat
quantity measurement can be activated.

A menu opens in which all adjustments required for
the heat quantity measurement can be made.
If the Flow rate sensor option is activated, the im-
pulse input or, if available, a Grundfos Direct Sensor™
can be selected. Grundfos Direct Sensors™ are only
available if they have been previously registered in the
In-/Outputs menu. The impulse rate must be adjusted
in that menu as well.
If the Flow rate sensor option is deactivated, the
controller calculates the heat quantity by means of a
fixed flow rate value. This is called heat quantity balan-
cing. For this purpose, the flow rate must be read from
the flowmeter at 100 % pump speed and adjusted in
the adjustment channel Flow rate. In addition to that,
a Relay must be allocated. Heat quantity balancing is
in effect whenever the allocated relay is active.
In the adjustment channel Fluid type, the heat trans-
fer fluid must be selected. If either Propylene glycol