16.2 Inputs

In this submenu, the type of the sensor connected can
be adjusted for each individual input. The following ty-
pes can be selected:
• Switch
• KTY
• Pt500
• RTA11M
• Pt1000
• None

If KTY, Pt500 or Pt1000 are selected, the channel
Offset appears, in which an individual offset can be
adjusted for each sensor.

Î

In order to adjust the offset, select the corres-
ponding menu item by pressing button

5

In- / Outputs / Inputs

Adjustment channel Description

Adjustment range / selection

Factory setting

S1 ... S12

Sensor input selection

-

-

Type

Sensor type selection

Switch, KTY, Pt500, RTA11M,
Pt1000, None

Pt1000

Offset

Sensor offset

-5.0 ... +5.0 K [-10.0 ... +10.0 °Ra]

0.0 K [0.0 °Ra]

Imp. 1 ... 3

Sensor type selection Imp 1 ... 3

Impulse, Switch, KTY, Pt500,
RTA11M, Pt1000, None

Impulse

Vol./Imp.

Impulse input selection

-

-

Type

Sensor type selection

Impulse, Switch, KTY, Pt500,
RTA11M, Pt1000, None

Impulse

CS10

CS10 input

-

-

Type

CS type

A ... K

E

Offset

Delete offset

Yes, No

No

Ga1, 2

Analog Grundfos Direct Sensor

TM

-

-

Type

Grundfos Direct Sensor

TM

type

RPS, VFS, None

None

Gd 1,2

Digital Direct Sensor

TM

type

-

-

Type

Grundfos Direct Sensor

TM

type

RPD, VFD, None

None

Min.

Minimum pressure (if Type = RPS)

0.0 ... 0.5 bar

0.0 bar

Max.

Maximum pressure (if Type = RPS)

0.1 ... 16.0 bar

0.6 bar

Min.

Minimum flow rate (if Type = VFS)

1 ... 39 l/min

2 l/min

Max.

Maximum flow rate (if Type = VFS)

2 ... 400 l/min

40 l/min

Î

To adjust the sensor offset, select the desired va-
lue by pressing buttons

or

4

, then confirm

by pressing button

5

CS sensor offset
If a CS10 irradiation sensor is to be connected, an

offset has to be carried out before the connection

is made.

To carry out the offset, proceed as follows:

Î

Adjust the CS type in the Type channel

Î

Select the Offset channel

Note:
If Grundfos Direct Sensors TM are used,

connect the sensor grounding common ter-
minal block with the protective grounding
conductor (see chap. 2.2).

Î

Confirm the reset enquiry with Yes

Î

Select back to return to the Inputs menu,

then connect the CS sensor

ATTENTION! System damage!

Selecting the wrong sensor type

will lead to unwanted controller

actions. In the worst case, system

damage can occur!

Î

Make sure that the right

sensor type is selected

for each input!