Pump is overheated, but no heat transfer from the collector to the store, flow
and return have the same temperature; perhaps also bubbling in the lines.

Air or gas bubbles in the system?

no

yes

Is the collector circuit blocked at

the dirt trap?

yes

Clean dirt trap

Pump starts for a short moment, switches off, switches on again, etc.

Temperature difference at the

controller too small?

no

yes

Wrong position of collector

sensors?

yes

Change ∆Ton and ∆Toff

correspondingly.

no

no

OK

Pump starts up very late.

The temperature diffrence between store and collector increases enormously
during operation; the collector circuit cannot dissipate the heat.

Collector circuit pump defec-

tive?

no

yes

Heat exchanger calcified?

yes

Check / replace it

Decalcify it

no

Heat exchanger blocked?

yes

no

Clean it

Heat exchanger too small?

yes

Change ∆Ton and ∆Toff

correspondingly.

Switch-on temperature diffe-

rence ∆Ton too large?

no

yes

Vent the system; increase the
system pressure to a static
primary pressure of at least
plus 0.5 bar (7.25 psi); if ne-
cessary continue to increase
pressure; switch the pump
off and on for a short time.

Plausibility control of
the option evacuated
tube collector special
function

Mount the collector sensor at
solar flow (warmest collector
output); use immersion sleeve
of the respective collector.

Replace with correctly
sized one.

Non-ideal position of the
collector sensor (e.g. flatscrew
sensor instead of sensor in
immersion sleeves).

yes

Activate evacuated tube
collector function if neces-
sary.

o.k.