Return preheating

The return preheating function can be used for trans-
ferring heat from a heat source to the heating circuit
return.
The allocated relay is energized when both switch-on
conditions are fulfilled:
• the temperature difference between the allocated

sensors has exceeded the switch-on temperature
difference

• the temperature at the outdoor temperature

sensor has fallen below the adjusted outdoor
temperature

With the summer switch-off option, the return pre-
heating can be suppressed outside the heating period.
If the heating circuit concerned is controlled by the
controller, the adjustments automatically adapt to the
heating circuit.

Sensor HS

Relay

Sensor
Return

Adjustment channel Description

Adjustment range / selection Factory setting

Relay

Relay selection

system dependent

system dependent

Sen. Return

Return sensor selection

system dependent

system dependent

Sen. HS

Heat source sensor selection

system dependent

system dependent

∆Ton

Switch-on temperature difference 2.0 ... 30.0 K [4.0 ... 60.0 °Ra] 6.0 K [12.0 °Ra]

∆Toff

Switch-off temperature difference 1.0 ... 29.0 K [2.0 ... 58.0 °Ra] 4.0 K [8.0 °Ra]

Summer off

Summer switch-off option

Yes, No

No

Sensor

Outdoor sensor selection

system dependent

system dependent*

Toff

Switch-off temperature

10 ... 60 °C [50 ... 140 °F]

20 °C [68 °F]

Funct.

Activation / Deactivation

Activ., Deactivated

Deactivated

Arrangement / Opt. functions / Add new function... / Ret. preheat.