Heat exchange

The heat exchange function can be used for transfer-
ring heat from a heat source to a heat sink.
The allocated relay is energized when all switch-on
conditions are fulfilled:
• the temperature difference between the allocated

sensors has exceeded the switch-on temperature
difference

• the temperature at the heat source sensor has

exceeded the minimum temperature

• the temperature at the heat sink sensor has fallen

below the maximum temperature

If ∆Tset is exceeded, pump speed control will come
into effect. For every deviation of 2 K [4 °Ra], the
pump speed will be adjusted by 10 %.

Sensor Source

Relay

Sensor Sink

Adjustment channel Description

Adjustment range / selection Factory setting

Relay

Relay selection

system dependent

system dependent

Sen. So.

Heat source sensor selection

system dependent

system dependent

Sen. Sink

Heat sink sensor selection

system dependent

system dependent

∆Ton

Switch-on temperature difference

1.0 ... 30.0 K [2.0 ... 60.0 °Ra] 6.0 K [12.0°Ra]

∆Toff

Switch-off temperature difference

0.5 ... 29.5 K [1.0 ... 59.0 °Ra] 4.0 K [8.0°Ra]

∆Tset

Set temperature difference

1.5 ... 40.0 K [3.0 ... 80.0 °Ra] 10.0 K [20.0°Ra]

Min. speed

Minimum speed

30 ... 100 %

30 %

Tmax

Maximum temperature of the store
to be loaded

10 ... 95 °C [50 ... 204 °F]

60 °C [140 °F]

Tmin

Minimum temperature of the store
to be loaded

10 ... 95 °C [50 ... 204 °F]

10 °C [50 °F]

Funct.

Activation / Deactivation

Activ., Deactivated

Deactivated

Arrangement / Opt. functions / Add new function... / Heat exchange