The CS bypass function is a different possibility to ac-
tivate the collector circuit bypass. To enable the use of
the CS bypass function, a CS10 irradiation sensor has
to be connected.
When the CS bypass function is activated, the irradia-
tion value is the switch-on condition for the collector
circuit bypass.
The relay remains switched on if the Irrad. value is
exceeded for the Delay time. When solar loading be-
gins or the irradiation value remains below the switch-
on value for the delay time, the relay is switched off.

CS bypass

Adjustment channel Description

Adjustment range / selection

Factory setting

Collector

Collector field

system dependent

system dependent

Irrad.

Switch-on irradiation

100 ... 500 W / m²

200 W / m²

Delay

Delay time

10 ... 300 s

120 s

Funct.

Activation / Deactivation

Activ., Deactivated

Deactivated

Solar / Opt. functions / Add new function... / CS bypass