The CS bypass function is a different possibility to ac-
tivate the collector circuit bypass. To enable the use of
the CS bypass function, a CS10 irradiation sensor has
to be connected.
When the CS bypass function is activated, the irradia-
tion value is the switch-on condition for the collector
circuit bypass.
The relay remains switched on if the Irrad. value is
exceeded for the Delay time. When solar loading be-
gins or the irradiation value remains below the switch-
on value for the delay time, the relay is switched off.
CS bypass
Adjustment channel Description
Adjustment range / selection
Factory setting
Collector
Collector field
system dependent
system dependent
Irrad.
Switch-on irradiation
100 ... 500 W / m²
200 W / m²
Delay
Delay time
10 ... 300 s
120 s
Funct.
Activation / Deactivation
Activ., Deactivated
Deactivated
Solar / Opt. functions / Add new function... / CS bypass