Does the warm water circula-

tion run for a very long time?

no

yes

Use the circulation pump with

timer and switch-off thermostat
(energy efficient circulation).

Circulation pump and blocking

valve should be switched-off for

1 night; less store losses?

yes

no

Check whether the pumps of the

backup heating circuit run at night;

check whether the non-return valve

is defective; problem solved?

no

yes

no

a

The gravitation circulation

in the circulation line is too

strong; insert a stronger valve

in the non-return valve or an

electrical 2-port valve behind
the circulation pump; the 2-port
valve is open when the pump is

activated, otherwise it is closed;

connect pump and 2-port valve
electrically in parallel; activate

the circulation again. Deactivate
pump speed control!

Clean or replace it.

Further pumps which are connec-
ted to the solar store must also be
checked.

Check the non-return valve in
warm water circulation - o.k.